DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 98
Bosch Security Systems | 8/04 | 4998153891C
Options 1 for Zone Function Type 4 (24-Hour Tamper)
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections: 0, 2, 8, 10
The 24-hour Tamper zone function type uses the following parameter option chart.
Enter This Data Digit to Select Options
24-hour Tamper Input Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected
Reserved
Voice Verification
Reserved
No EOL Resistor Required
• •
See the option descriptions for “Voice Verification” and “No EOL Resistor Required” in Options 1 for Zone
Function Type 3 (24-hr Control Input) on page 97.
Options 1 for Zone Function Type 10 (Controlled Keyswitch)
Address: See Table 17
Default: 8 (Momentary, All On, Off from Any Armed State)
Selections:
0 = Maintained, All On, Off from Any Armed State
1 = Maintained, All On, No Off
2 = Maintained, No On, Off from Any Armed State
4 = Maintained, Perimeter Only, Off from Any Armed State
5 = Maintained, Perimeter Only, No Off
6 = Maintained, No On, Off from Perimter Only or Partial On Arming
8 = Momentary, All On, Off from Any Armed State
9 = Momentary, All On, No Off
10 = Momentary, No On, Off from Any Armed State
12 = Momentary, Perimeter Only, Off from Any Armed State
13 = Momentary, Perimeter Only, No Off
14 = Momentary, No On, Off from Perimeter Only or Partial On Arming
15 = Exit Terminator Button
Momentary Keyswitch: To silence alarms (stop Alarm output), operate the keyswitch. If the area is armed,
operating the keyswitch to silence the alarm also disarms the area. If the area is disarmed, operating a
momentary keyswitch to silence the alarm does not arm the area.
Maintained Keyswitch: To silence alarms (stop Alarm output) while the area is armed, turn the keyswitch to
the disarmed position. The control panel disarms the area and silences alarms. To silence alarms (stop Alarm
output) while the area is disarmed, turn the keyswitch to the armed position (the control panel does not arm)
and then return to the disarmed position.
Exit Terminator Button: This zone function activates in the same manner as the momentary keyswitch.
When Exit Delay is active, operating the exit terminator button terminates Exit Delay and immediately arms
the control panel. If Chime Mode is enabled and Exit Delay is not active, pressing the exit terminator button
activates the chime tone and the button functions as a doorbell.