Zone Doubling Programming
Zone doubling requires 3.65 k Ω and 2.2 k Ω EOL resistors as shown in Table 13. If zone doubling is
not used, see On-board Location EOL Resistor Value on page 103, and DX2010 Configuration
Options on page 127, for on- and off-board zone EOL resistor configuration. For proper zone doubled
wiring, see the DS7200V2 Installer’s Guide (P/N: 4998153893).
To use both on-board and off-board zone doubling at the same time, use the following steps:
1. Double Locations 1 to 8 with Locations 9 to 16.
a. Set the Device Type for Locations 1 to 16 to 1 (on-board).
b. Set Address 1026 (On-board Location EOL Resistor Value) to 4 (Zone doubled, 2.2 k & 3.65 k
EOL resistors).
c. Use 3.65 k EOL resistors on Locations 1 to 8, and 2.2 k EOL resistors on Locations 9 to 16.
2. Double Locations 25 to 32 with Locations 33 to 40.
a. Set the Device Type for Locations 25 to 40 to 3 (DX2010 zone doubled).
b. Set the DX2010’s DIP switches to Address 107 (Locations 25 to 40). See Table 14.
c. Use 3.65 k EOL resistors on Locations 25 to 32, and 2.2 k EOL resistors on Locations 33 to 40.
Locations 17 to 24 cannot be used for zone doubling when doubling on-board and off-board zones at
the same time. These locations can still be used as RF zones, or as non-doubled zones.
Table 14: DX2010 DIP Switch Settings
DX2010 DIP Switch Settings
DIP
Switches
S1 S2 S3 S4 S5 S6
Module
Address
32 16 8 4 2 1
101 OFF OFF OFF OFF OFF OFF
102 OFF OFF OFF OFF OFF
ON
103 OFF OFF OFF OFF
ON
OFF
104 OFF OFF OFF OFF
ON ON
105 OFF OFF OFF
ON
OFF OFF
106 OFF OFF OFF
ON
OFF
ON
107 OFF OFF OFF
ON ON
OFF