DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 90
Bosch Security Systems | 8/04 | 4998153891C
Zone Function Type, Zone Function
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections: 0 to 15 (see Table 20)
See Table 20 for a description of each zone function type and the events and reports associated with that Zone
Function type, when the zone is wired using one of the following configurations: single EOL resistor, tamper-
wired, zone-doubled, or no EOL resistor.
Controlled Zone: Controlled zones are turned on and off when the user turns the system on (armed) and off
(disarmed).
24-hour Zone: 24-hour zones are always on and cannot be turned off by the user.
Table 20: Zone Function Type Options
Zone Function Type Wiring
Configuration
Description Events/Reports
0
Chime
Mode Only
Single EOL
Resistor
No alarm or trouble response to opens or shorts (Chime Mode
only).
No events/reports.
Tamper-Wired,
Zone-Doubled,
No EOL Resistor
No alarm or trouble response to faults (Chime Mode only).
1 24-hr Fire
Single EOL
Resistor
Short on sensor loop starts Fire Alarm response. Open on sensor
loop starts trouble response. Activates Fire Alarm Output
(Temporal Code 3).
Tamper-Wired,
Zone-Doubled,
No EOL Resistor
Fault on sensor loop starts Fire Alarm response. Activates Fire
Alarm Output (Temporal Code 3).
Fire Alarm {75-77}, Fire Missing {78}, Fire
Restore from Alarm {79}, Fire Restore
from Missing {174}, Fire Trouble {80},
Fire Trouble Restore {81}, Fire Bypass
{26-27}, Swinger Shunt {33}, Restoral
from Swinger Shunt {173}, Fire
Unbypass {34}
2
24-hour
Fire with
Alarm
Verification
Single EOL
Resistor
Short on sensor loop starts the verification process.
Control panel activates Fire Verification output function for 15
sec to reset smoke detectors. See
Table 25 on page 112 for
Fire Verification Output Function information.
Short on sensor loop within 120 sec of reset starts alarm
response. If zone remains normal or open for the 120-second
verification window, there is no alarm response.
Open on sensor loop starts trouble response.
Activates Fire Alarm Output (Temporal Code 3).
Fire Alarm {75}, Fire Unverified {77}, Fire
Missing {78}, Fire Restore from Alarm
{79}, Fire Restore from Missing {174},
Fire Trouble {80}, Fire Trouble Restore
{81}, Fire Bypass {26-27}, Fire Unbypass
{34}
Tamper-Wired,
Zone-Doubled,
No EOL Resistor
Fault on sensor loop starts the verification process.
Control panel activates Fire Verification output function for 15
sec to reset smoke detectors. See Table 25 on page 112 for
Fire Verification Output Function information.
Fault on sensor loop within 120 sec of reset starts alarm
response. If zone remains normal for the 120-second verification
window, there is no alarm response.
Activates Fire Alarm Output (Temporal Code 3).
Fire Alarm {75}, Fire Unverified {77}, Fire
Missing {78}, Fire Restore from Alarm
{79}, Fire Restore from Missing {174},
Fire Bypass {26-27}, Fire Unbypass {34}
3
24-hr
Control
Input
Single EOL
Resistor
Can be used to control various system functions. See Options 1
for Zone Function Type 3 (24-hr Control Input) on page 97 for
more information. Only Trouble on Open option is available.
Trouble {139}, Trouble Restore {146}
Tamper-Wired,
Zone-Doubled,
No EOL Resistor
Can be used to control various system functions. See Options 1
for Zone Function Type 3 (24-hr Control Input) on page 97 for
more information.
No events/reports.