DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 32
Bosch Security Systems | 8/04 | 4998153891C
Automatic Test {137} Report Interval
Address: 0254
Default: 3 (7 Days)
Selections:
0 = No Automatic Test
1 = 1 H
2 = 1 Day
3 = 7 Days
4 = 28 Days
Enter zero (0) to disable Automatic Test {137} reporting.
The one-hour interval is incremented on the minute. For example, if you set the Automatic Test Time parameter
to 1020 (10:20 am), the Automatic Test Interval is one hour, and left programming mode at 11:10, then the
control panel sends a test report at 11:20 am (less than one hour after leaving programming mode). The next test
report would come at 12:20 pm.
The one-day, seven-day and 28-day intervals are incremented at midnight (2400). For example, if you set the
Automatic Test Time parameter to 1020 (10:20 am), the Automatic Test Interval is one day, and left programming
mode at 10:10 am, then the control panel does not send a test report until 10:20 the next day (after the one-day
interval increment at midnight).
Test Report Routing
Address: 0255
Default: 1 (Reports to Destination 1, Events to Log/Printer)
Selections:
0 = No Reports, no Events to Log/Printer
1 = Reports to Destination 1, Events to Log/Printer
2 = Reports to Destination 2, Events to Log/Printer
3 = Reports to Destinations 1 & 2, Events to Log/Printer
4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
5 = No reports, Events to Log/Printer
This is a global (affects all areas) parameter.
Test reports include the System Test {137}/{138} reports. The Walk Test Start {158} and Walk Test End {159}
reports follow their own routing.
Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).