DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 11
Bosch Security Systems | 8/04 | 4998153891C
• Address: See Table 5
• Default: See Table 5
• Selections: 0 to 15
Table 5: Personal Dialing Format Configuration
Event Group Address Personal Dialing Format Code Data Digit Default
1 3414 Duress 0
2 3415 Fire Alarm 1
3 3416 Non-fire Alarm 2
4 3417 Reserved 0
5 3418 Fire Trouble 5
6 3419 Non-fire Trouble 6
7 3420 Fire Restoral 0
8 3421 Non-fire Restoral 0
9 3422 RF Trouble 0
10 3423 Open/Close 0
11 3424 Installer Mode 0
12 3425 System Fault 8
13 3426 Test Report 0
14 3427 Reserved 0
15 3428 Bypass 0
16 3429 Output/User 0
Use this parameter to select the tone for the 16 different Personal Dialing Format event groups.
For each event group, the report is programmed as a value from 0 to 15. If 0 (zero) is programmed, no report is
sent and the event is a Local Only event.
See Table 6 for the two-digit report tone when the value entered is non-zero (1to15).
Table 6: Report Tone Selections
Data Digit Selection Report Tone
0 None
1 1 0
2 1 1
3 2 0
4 1 2
5 2 1
6 3 0
7 1 3
8 2 2
9 3 1
10 4 0
11 1 4
12 2 3
13 3 2
14 4 1
15 5 0
Commentaires sur ces manuels