DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 119
Bosch Security Systems | 8/04 | 4998153891C
Steady, Pulse, and One-Shot Mode Configuration
• Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier parameters
below.
• Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based on the
values in the Base and Multiplier columns (see Table 27). The duration, or On Time, of an output is
determined by selecting one of the four Base options from Table 27. Calculate the Off Time by multiplying the
Base by the Multiplier.
The Time Base of 200 ms in Table 27 and Table 28 is only available for on-board outputs.
Table 27: Pulse Mode Configuration
Base On Time
(On Time = Time of Base)
Multiplier Off Time
(Off Time = Base x Multiplier)
Tolerance
0 0 N/A Always Off N/A
1 (200 ms) 200 ms 01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 1 second 01 to 99 1 to 99 sec ±1 second
3 (1 min) 1 minute 01 to 99 1 to 99 min. ±1 minute
4 (1 hr) 1 h 01 to 99 1 to 99 h ±1 h
• One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying the Base
by the Multiplier.
Table 28: One Shot Mode Configuration
Base Multiplier On Time
(On Time = Base x Multiplier)
Tolerance
0 N/A 0 N/A
1 (200 ms) 01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 01 to 99 1 to 99 sec ±1 second
3 (1 min) 01 to 99 1 to 99 min. ±1 minute
4 (1 hr) 01 to 99 1 to 99 h ±1 h