DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 21
Bosch Security Systems | 8/04 | 4998153891C
AC Power Supervision Options
Address: 0223
Default: 4
Selections: 0 to 15
Enter This Data Digit to Select Options
AC Power Supervision Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected
AC Fail Report is Tag-along
• • • • • • • •
Disable AC Fail Local Annunciation (at keypad)
Enable Arm/Disarm/Bypass Tracking
• • • • • • • •
Enable Internal Crystal to Keep Time
• • • • • • • •
This parameter configures the control panel’s local response to AC power failure.
AC power must be failed for a maximum of 10 sec before the control panel responds to the failure. It must be
restored for a maximum of 10 sec before the control panel responds to the AC restoral. See AC Fail Report Delay
on page 34 for instructions on delaying the AC Fail Report.
The trouble tone for AC fail events sounds at all keypads in all areas. However, the trouble tone must be
silenced in each area. Silencing the trouble tone in one area does not silence it in the other areas.
AC Tag-along: If this option is enabled, AC Fail and Restoral reports are not sent at the time of the event,
but are sent as ‘tag-along’ reports with the next report to be sent.
Disable AC Fail Local Annunciation (at Keypad): If the control panel is only powered from a DC power
source (through battery connections), select Option 2, “Disable AC Fail Local Annunciation.” This prevents
the control panel from annunciating AC failures locally at the keypad. You must also disable AC Fail
reporting at the next parameter, “AC Fail, Low Battery Report Options.”
Enable Arm/Disarm/Bypass Tracking: If If this option is not enabled, the control panel always powers up
in the disarmed state (Off), even if the control panel was armed before powering down. Zones that were
bypassed before powering down are not bypassed at power-up.
Enable Internal Crystal to Keep Time: Not enabling this option keeps time by looking at the Mains AC
power. Enable this option if running on DC only (for example, if you are generating your own power or
power cycles are not consistent), otherwise leave set to default.