DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 30
Bosch Security Systems | 8/04 | 4998153891C
Walk Test Configuration Options
• Address: 0246
• Default: 8
• Selections: 0 to 15
Enter This Data Digit to Select Options
Walk Test Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Walk Test Disabled
•
Start with System Test
• • • • • • • •
Include Fire Zones
• • • • • • • •
Include 24-hour Zones
• • • • • • • •
Include Controlled Zones
• • • • • • • •
When a user enters the Walk Test key sequence ([#][4][4]) at a keypad to start a walk test, the system includes the
option(s) selected in this parameter. If included, the “Start with System Test” option follows its own configuration.
See System Test Configuration Options on page 28 and System Test Enable Options on page 29. No reports are sent from
zones included in the test.
If a Zone Function type is not included, those zones remain active during the test.
A Walk Test Start {158} report, with user number, is sent at the start of the test. A Walk Test End {159} report,
with User Number 0 (zero), is sent at its conclusion.
Entering Walk Test mode starts a 20-minute timer. After 15 min. with no activity from the included zones, a
warning tone (same as Auto-arm warning) begins. After 20 min., the test automatically terminates with User
Number 0 (zero).
Any fire or 24-hour zone faulted at the termination of the test generates a trouble response, not an alarm
response. If programmed for alarm reports but not trouble reports, trouble reports are sent as part of the
trouble response only in this instance.
Walk Test Enable Options
• Address: 0247
• Default:
− DS7240V2: 15
− DS7220V2: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Walk Test Enable Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Walk Test Disabled
•
Walk Test Enabled for Area 1
• • • • • • • •
Walk Test Enabled for Area 2
• • • • • • • •
Walk Test Enabled for Area 3 (DS7240V2 only)
• • • • • • • •
Walk Test Enabled for Area 4 (DS7240V2 only)
• • • • • • • • •
Use this parameter to choose which areas have the Walk Test function ([#][4][4]) enabled. Although the
configuration of Walk Test is global, the function is only enabled for keypads in the areas selected here, and only
for users with the proper authority level. See Authority Level Option 9: System Functions 1 on page 57 for more
information.
Commentaires sur ces manuels