DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 49
Bosch Security Systems | 8/04 | 4998153891C
Area # Opening {89-96}/Closing {42-67} Reporting Options
• Address:
− Area 1: 0296
− Area 2: 0318
− Area 3 (DS7240V2 only): 0340
− Area 4 (DS7240V2 only): 0362
• Default: 1
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Area # Open/Close Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Open or Close Reports for Area #
•
Open/Close Reports (for All On) for Area # Enabled
•
• • • • • • •
Restrict Open/Close Reports; Open after Alarm,
Close on Force Arm
• • • •
Open/Close Reports for Perimeter Only (and Partial
On) Mode – Must also select Open/Close Reports (for
All On)
• • • •
1 Second Bell Test on Closing Rpt Acknowledgement
• • • •
• Open/Close Reports for Area # Enabled: If enabled, this option configures Opening/Closing reports for
each area. This also includes the report for the Extend Auto Closing {21} event. Opening {89 to 96} and
Closing {42 to 67} reports must be enabled at the system level. Opening and Closing reports are also enabled
by authority level. Reporting must also be enabled at the system level (see Global Reporting Options on page
19).
• Restrict Open/Close Reports; Open From Alarm, Close on Force Arm: If this option is enabled, the
control panel only sends opening reports when the user disarms the system after an alarm and when Bell
Time has expired. The control panel only sends closing reports when a zone is force-armed. Force arming is
set by authority level and by zone function configuration.
Enabling the “Restrict Open/Close Reports” option overrides the “First Area to Open/Last Area to
Close Reporting” option. See Arming Options 2 on page 38 for more information on the “Restrict
Open/Close Reports” option.
• Open/Close Reports for Perimeter Only Mode: If this option is enabled, the control panel sends closing
reports when users arm the system Perimeter Only. If any zones are bypassed, bypass reports are also sent.
The control panel sends opening reports when users disarm the system. Perimeter Only arming is set by
authority level and by Zone Function configuration.
• 1 Second Bell Test on Closing Ack: If this option is enabled, outputs assigned to Alarm Output Functions
1|8, 1|9, 1|10, and 8|8 activate for one sec. See Function, Output ## on page 112 for output function
descriptions.