DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 87
Bosch Security Systems | 8/04 | 4998153891C
RF Transmitters and Zone States
With the exception of the point transmitter, all RF transmitters show only two electrical zone states (Normal and
Faulted).
The RF3401E Point Transmitter can monitor both a reed switch (magnet) and a supervised sensor
loop. After the door/window transmitter's ID is added, the control panel shows one of the following
status messages depending on how the door/window transmitter is configured:
- "No magnet, no loop": the reed switch is open (no magnet is present), and there is no device
connected to the sensor loop
- "Reed switch closed": the reed switch is closed by a magnet
- "Loop closed": a device is connected to the sensor loop
- "Reed closed, loop closed": the reed switch is closed by a magnet, and a device is connected to
the sensor loop
The RF3405E Inertia Transmitter operates similarly as the RF3401E described above, however the
RF3405E can monitor both a reed switch (magnet) and a supervised sensor loop or a reed switch and
an inertia sensor loop. It cannot monitor a supervised sensor loop and an inertia sensor loop.
For this example, mount the point transmitter on a doorjamb, and mount its magnet on the door. Close the door
to place the magnet next to the reed switch. The control panel now recognizes the reed switch to be in a normal
(not faulted) state. From this point forward, it shows the zone (door/window transmitter) as shorted (faulted)
whenever it sees the reed switch faulted. It shows the zone as normal when the reed switch returns to normal,
even though the sensor loop remains faulted.
To continue with this example, connect a contact on a window near the door. Wire the contact and the EOL
resistor to the Door/Window transmitter’s sensor loop and close the window. The control panel now recognizes
the sensor loop to be in a normal (not faulted) state. From this point forward, it shows the zone (door window
transmitter) as faulted whenever it sees either the sensor loop or the reed switch faulted. It only shows the zone as
normal when both the reed switch and the sensor loop return to normal. When only the reed switch is monitored,
only the Normal and Shorted (Faulted) zone states are shown.
Cut out reed switch if not used.
Disabling a Zone (RF or Wired)
To disable a wired or wireless (RF) zone, do any of the following:
• Set the location’s device parameter to 0 (zero). See Location ##, Device on page 83.
• Set the location’s zone function parameter to 0 (zero). See Location ##, Zone Function on page 84.
• Set the location’s area parameter to 0 (zero). See Location ##, Area on page 85.