DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 69
Bosch Security Systems | 8/04 | 4998153891C
Keypad/Door Access Control Module (DACM) Area Options
Address:
Keypad/DACM 1: 0679
Keypad/DACM 2: 0681
Keypad/DACM 3: 0683
Keypad/DACM 4: 0685
Keypad/DACM 5: 0687
Keypad/DACM 6: 0689
Keypad/DACM 7: 0691
Keypad/DACM 8: 0693
Default:
Keypad/DACM 1: 1 (Device is a keypad assigned to Area 1)
Keypads/DACMs 2 to 8: 0 (No keypad/DACM assigned)
Selections: 0 to 4, 9 to 12
Enter This Data Digit to Select Options
Keypad/DACM Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Keypad/DACM not assigned (disabled)
Assign Keypad/DACM to Area 1
Assign Keypad/DACM to Area 2
Assign Keypad/DACM to Area 3 (DS7240V2 only)
Assign Keypad/DACM to Area 4 (DS7240V2 only)
Device is a Keypad
• • • •
Device is a DACM
• • • •
Assign only one area to each keypad. Users (PINs) can be assigned to multiple areas. The Move to Area function
([#][5][0]) allows users (PINs) assigned to multiple areas to view those areas from one keypad.
The control panel supervises the connection to the DACM. If it fails to communicate with the control panel, the
control panel sends a “Dbus Missing” {125} report.
See the documentation supplied with the DACM for complete installation, programming, addressing, and
operation instructions.
The control panel supports up to 8 DACMs. However, each DACM added to the system replaces one
keypad. If 8 DACMs are added, you cannot add a keypad. For full system control, make sure at least
one text keypad is included in the system.