DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 105
Bosch Security Systems | 8/04 | 4998153891C
Swinger Count for Zone Reports
Address: 1030
Default: 3
Selections:
0 (Swinger disabled)
1 to 15
This parameter sets the swinger count for zone alarm, trouble, and restoral reports.
Swinger shut down for the dialer is a global function that affects all zones.
Swinger Shunt {33} reports are sent for Swinger Shunt of zones.
The Swinger Count is reset on both arming and disarming, allowing the Swinger Shunt feature to work for both
non-24-hour and 24-hour zones.
Example: Assume the Swinger Shunt option is enabled, the control panel is armed and there are no alarms. When
the zone sends an Alarm or Trouble event to the dialer, the swinger count for zone reports is checked. If the
counter is at zero, the zone is already Swinger Shunted and no report is sent. If the counter is not at zero, the
control panel decrements the counter. If the counter then goes to zero after the report is sent, the Swinger Shunt
{33} report is sent. The zone is then swinger shunted.
If the swinger count is set to zero (0), the Swinger Count for Zone Reports feature is disabled. The dialer sends all
alarm or trouble events.
Bypass/Swinger Shunt/Trouble Report Options
Address: 1031
Default: 3
Selections: 0 to 15
Enter This Data Digit to Select Options
Bypass, Swinger Shunt, Sensor Trouble Report Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected
Zone Bypass and Swinger Shunt Reports Enabled
• • • • • • • •
Bypass and Swinger Shunt Restoral Reports Enabled
Sensor Trouble Reports Enabled
• • • • • • • •
Sensor Trouble Restoral Reports Enabled
• • • • • • • •
This is a global parameter that affects all areas. This parameter enables Zone Bypass, Swinger Shunt and Sensor
reports (and their respective restoral reports are enabled).
Sensor Monitor Time
Address: 1032, 1033
Default: 0,7
Selections: 0 to 9
This parameter determines the number of days (00 to 99) that the control panel can function without sensor (zone)
activity (time accumulates only when the area is off/disarmed).
Assign this parameter by zone function in Options 1, Zone Function ## (see page 95). This parameter does not apply
to fire zone types or non-fire 24-hour zone types.
If there is no sensor activity after the entered time period, a trouble report is sent.