Bosch DS7200V2-EXP Guide de l'utilisateur Page 140

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 156
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 139
DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 140
Bosch Security Systems | 8/04 | 4998153891C
Table 31: Control Panel Events and Reporting Formats (continued)
Event Event as shown in
Control Panel Log
SIA Report Contact ID
Report
Event Description Zone Types
Linked to Event
RPS
Event
Group
Status
Report
33 Bypass,Swinger
BB Burglary
Bypass
575 Swinger
Shunt
Zone Swinger Shunted. All zone types 15
34 UnBypss,Fire, Usr FU Fire UnBypass
571 Fire
bypass
User cleared bypass (unbypass),
Fire zone types.
1- Fire
2- Fire with
Alarm
Verification
15
35 UnBypss,Ctrl,Usr
BU Burglary
Unbypass
570
Zone/Sensor
bypass
User cleared bypass (unbypass),
controlled zone types.
10 to 15- Zone
Types
15
36 UnBypss,24hr,Usr
BU Burglary
Unbypass
572 24-Hr
Zone Bypass
User cleared bypass (unbypass),
24-hour zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
37 Call for Service
YX Service
Required
616 Service
Request
This report sent automatically at
Call for Service Interval. It does not
indicate a trouble condition.
12 R
38 Cancel Alarm
BC Burglary
Cancel
406 Cancel
User acknowledged active alarm
before Bell Time expired, non-fire
zone types.
8
39 Cancel Fire FC Fire Cancel 406 Cancel
User acknowledged active alarm
before Bell Time expired, fire zone
types.
7
40 CheckSum Fail
YF Parameter
Checksum Fail
303 RAM
Checksum Bad
Checksum on panel’s parameters
failed. Panel program should be
verified.
12 R S
41 ChkSum Fail,DBus
YF Parameter
Checksum Fail
330 System
Peripheral
trouble
Checksum on Data Bus device
parameters failed. Device should
be checked.
12 R S
42 Cls,All,+Dly,Skd
CA Automatic
Closing
403 Automatic
O/C
System turned All On with
Entry/Exit Delay by Sked.
10
43 Cls,All,+Dly,KS
CS Closing
Keyswitch
409 Keyswitch
O/C
System turned All On with
Entry/Exit Delay by Keyswitch.
10
44 Cls,All,+Dly, RPS
CQ Remote
Closing
400
Open/Close
System turned All On with
Entry/Exit Delay by RPS.
45 Cls,All,+Dly,Tel
CQ Remote
Closing
407 Remote
Arm/Disarm
System turned All On with
Entry/Exit Delay by Telephone.
10
46 Cls,All,+Dly,Usr
CL Closing
Report
401 O/C by
User
System turned All On with
Entry/Exit Delay by User.
10
47 Cls,All,-Dly,RPS
CQ Remote
Closing
400
Open/Close
System turned All On with no delay
(instant) by RPS.
48 Cls,All,-Dly,Usr
CL Closing
Report
401 O/C by
User
System turned All On with no delay
(instant) by User.
10
49 Cls,Prt,+Dly,Skd
CA Automatic
Closing
456 Partial Arm
System armed Perimeter Only with
Entry/Exit delay by Sked.
10
50 Cls,Prt,+Dly,KS
CS Closing
Keyswitch
442 Keyswitch
Armed Stay
System armed Perimeter Only with
Entry/Exit Delay by Keyswitch.
10
51 Cls,Prt,+Dly, RPS
CQ Remote
Closing
456 Partial Arm
System armed Perimeter Only with
Entry/Exit Delay by RPS.
52 Cls,Prt,+Dly,Usr
CL Closing
Report
456 Partial Arm
System armed Perimeter Only with
Entry/Exit Delay by User.
10
53 Cls,Prt,-Dly, RPS
CQ Remote
Closing
456 Partial Arm
System armed Perimeter Only with
no delay (instant) by RPS.
Vue de la page 139
1 2 ... 135 136 137 138 139 140 141 142 143 144 145 ... 155 156