DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 97
Bosch Security Systems | 8/04 | 4998153891C
Options 1 for Zone Function Type 3 (24-hr Control Input)
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections: 1 to 4, 9 to 12
The 24-hour Control Input zone function type uses the following parameter option chart.
Enter This Data Digit to Select Options
24-hour Control Input Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Voice Active Control Input
Alternate Communication Path Fault Input
Alarm Reset Control Input
Silence Outputs Control Input
No EOL Resistor Required
• • • •
Voice Active Control Input: If enabled, this option functions as a Voice Active zone. The control panel
must be off-hook and sending a report from a zone with the Voice Verification option selected. If the input
goes into “alarm” within 30
sec after the report is sent, all alarm outputs and keypad sounders assigned to the
same area as the input zone are silenced. Activation of this input does not create any events in the history log
or send any reports. When the input restores from “alarm,” the audible devices will resume sounding if any
bell time remains. The keypad sounders return to the alarm sound.
Alternate Communication Path Fault Control Input: If enabled, this option allows various external
modules to be connected for sending reports. This option also allows an external module to signal that it is
unable to send reports. When this option goes into “alarm,” the control panel initiates a System Trouble
condition. Event 167 is placed in the history log and its report is sent if there is means of sending the report.
When this input restores from “alarm,” Event 168 is placed in the history log and its report is sent. The
System Trouble condition clears based on the configuration of the “Phone Line Fault Requires Reset” option
(see Phone Line Options on page 14).
Alarm Reset Control Input: If enabled, this option allows the ARC to communicate with the control panel
through an external module and remotely reset the area. This reset can only occur if the control panel is
disarmed. Activation of this option does not create any events in the history log or send any reports.
Silence Outputs Control Input: If enabled, this option functions as a bell silence zone. When the input goes
into “alarm,” all alarm outputs and keypad sounders assigned to the same area as the input zone are silenced.
The conditions are silenced as soon as the input goes active. Activation of this input does not create any
events in the history log or send any reports. When the input restores from “alarm,” the audible devices
resume sounding if any bell time remains. The keypad sounders return to the alarm sound.
No EOL Resistor Required: This option determines whether the input zone functions with normal EOL
resistor supervision or without any EOL resistor supervision.