DS7400XiV4-EXP | Reference Guide | 2.0 Specifications EN | 9
Bosch Security Systems | 1/05| 4998154963B
Table 2: Specifications (continued)
Description Value
Fire Signal Initiating
Circuit
(2-wire mode)
Fire circuit works with 2- or 4-wire
detectors and has optional alarm
verification.
• Number of circuits: 8 on-board
• Type of circuit: Class B,
latching
• End-of-line resistor: 2.2 k Ω
(P/N 25899, provided)
• Supervisory current: 5.5 mA
• Maximum short circuit current:
22 mA
• Maximum line resistance: 60 Ω
• Circuit voltage range: 8.5 VDC
to 14.1 VDC
• Total detector standby current:
2.5 mA
Multiplex Bus Wiring
Requirements
5
• 0.8 mm (#22 AWG). Up to
610 m (2000 ft.) per system.
• 1.0 mm (#18 AWG). Up to
1525 m (5000 ft.) per system.
Multiplex Zone
Sensor Loop Wiring
Maximum wire length not to exceed
150 m (500 feet) regardless of the
wire gauge.
Option Bus Wiring
Requirements
Maximum wire length 305 m
(1000 feet) per home-run.
Maximum Load
Currents
See Table 3.
Backup Battery
Calculation
Use Table 4 to calculate the
standby battery capacity when using
the DS7400Xi.
Standby Current
Load
See Table 5.
NOTES:
1
= The total current output capacity for all auxiliary
devices, including keypads and smoke detectors = 1.5 A
standby, 2.5 A alarm. These ratings are maximum values.
The total combined output cannot exceed the maximum
load current.
2
= Current draw should be subtracted from either
maximum auxiliary or maximum alarm current draw.
3
= No more than 2 keypads (0.8 mm/#22 AWG) or 3
keypads (1.0 mm/#18 AWG) are recommended on any
305 m (1000 ft.) run.
4
= Shared cable is not recommended for keypad,
multiplex, options bus, telephone, or siren wiring.
5
= Do not use twisted-pair or shielded cable. Do not share
cable with the keypad lines.
2.1 Maximum Load Currents
Table 3: Maximum Load Currents
Maximum Load
Currents
Standby Alarm
Maximum Current by Output:
Not to exceed the maximum load currents listed above in
Standby or Alarm.
Aux. Power and
Keypad
(combined)
1.0 A 1.0 A
Option Power 1.0 A 1.0 A
Bell Output — 1.75 A
Programmable
Output 2
500 mA 500 mA
Loop Power 500 mA 500 mA
2.2 Backup Battery Calculation
Use Table 4 to calculate the standby battery capacity
when using the DS7400Xi.
2.3 Standby Current Load
See Table 5:
• Battery Ah – (20% storage + 0.375 Ah Alarm)
• Table 5 shows the derated battery divided by hours
minus the control panel standby (175 mA).