DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 51
Bosch Security Systems | 1/05| 4998154963B
5.9.15 Commercial Fire Mode Programming
This section describes how to define the parameters for the Commercial Fire Mode.
See Section 7.2.11 Commercial Fire Mode Programming for Commercial Fire Mode Programming glossary definitions.
• Address: 2733
• Data Digit:
• Data Digit 1: ____ (see Table 65)
• Data Digit 2: ____ (see Table 66)
• Default: 0
• Selections: 0 to 9, *0 to *2 (hexadecimal values that display as A through C at the keypads)
Table 65: Commercial Fire Mode Programming (Address 2733, Data Digit 1)
Selections for Data Digit 1
Select Options 0 1 2 3 4 5 6 7 8 9 *0 *1 *2
Commercial Fire Mode Disabled
•
Local Commercial Fire Mode Enabled
• • •
• • •
Central Station Commercial Fire Mode Enabled
• • • • • •
10 Second Delay on Waterflow Zone
•
•
20 Second Delay on Waterflow Zone
•
•
30 Second Delay on Waterflow Zone
•
•
40 Second Delay on Waterflow Zone
•
•
50 Second Delay on Waterflow Zone
•
•
Table 66: Commercial Fire Mode Programming (Address 2733,
Data Digit 2)
Selections for
Data Digit 2
Select Options 0 1 2 3 4 5
Bell and Auxiliary Activate on Fire
• • • •
• •
Bell and Auxiliary Activate on Burg
•
• •
Pulsing Fire Alarms are 1 Sec On/1 Sec Off
•
•
Pulsing Fire Alarms use California March Time
•
•
Pulsing Fire Alarms use Temporal Cadence
•
•
When programming fire zones, it is recommended that they be Zone Functions 12 and 13. See
Sections 5.9.1 Zone Function Programming, 5.9.2 Zone Programming: Assigning a Zone Function to
the Zone, and Regardless of Which Commercial Fire Mode is Chosen on page 52.
When Central Station Commercial Fire Mode is Chosen
When Central Station Commercial Fire Mode is chosen, Address 4021 (DS7420i: Dual Phone Line/Bell
Supervision Module Output Programming), will be forced to a value of 5.
When Local Commercial Fire Mode is Chosen
When Local Commercial Fire Mode is chosen, Address 4021 (DS7420i: Dual Phone Line/Bell Supervision
Module Output Programming) will be forced to a value of 3, 4, or 5 (turns the Bell Monitor feature ON and the
Alarm Output on Line Fault feature OFF).