
DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 32
Bosch Security Systems | 1/05| 4998154963B
Table 19: Keyswitch Programming (Address 0001
to 0030, Data Digit 1, if Data Digit 2 = 9)
Select Options Value
Single Partition – No Force Arm 0
Single Partition – Can Force Arm 1
All Partitions – No Force Arm 2
All Partitions – Can Force Arm 3
Table 20: Address 0001 to 0030 Zone Function Default Values
Value
(fill in)
Zone
Function
Address Default Values
(will be forced to different values when in Commercial Fire Mode; see
Section 5.9.15 Commercial Fire Mode Programming for more information)
1 0001 2 = Steady alarm output, alarm on short and open.
3 = Entry/exit delay 1.
2 0002 2 = Steady alarm output, alarm on short and open.
4 = Entry/exit delay 2.
3 0003 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
4 0004 2 = Steady alarm output, alarm on short and open.
5 = Interior entry/exit follower.
5 0005 2 = Steady alarm output, alarm on short and open.
6 = Interior home/away.
6 0006 2 = Steady alarm output, alarm on short and open.
7 = Interior Instant.
7 0007 2 = Steady alarm output, alarm on short and open.
2 = 24-Hour.
8 0008 7 = Pulsing alarm output, alarm on short, trouble on open.
A = Fire zone with verification.
9 0009 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
10 0010 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
11 0011 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
12 0012 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
13 0013 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
14 0014 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
15 0015 2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
16 to
30
0016 to
0030
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
Commentaires sur ces manuels