DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 28
Bosch Security Systems | 1/05| 4998154963B
5.0 Programming the Control
Panel
5.1 Entering Programmer’s Mode
To enter the Programmer's Mode, enter the
Programmer’s Code followed by [#][0]. Shorting the
program pads (see Section 3.0 Control Panel Installation
for location) on the control panel also enters
Programmer’s Mode.
The default Programmer’s Code is
[9][8][7][6]. If the system is reprogrammed
for 6-digit PINs, the default Programmer’s
Code is [9][8][7][6][5][4].
5.2 Reading Back a Program Address
To read back the value of a program address, enter that
program address followed by [#]. Each data digit is
displayed one data digit at a time. To view the second
data digit, press the [#] button again.
Figure 12 shows a sample display.
Figure 12: Program Address Display
P
r
o
g
.
M
o
d
e
4
.
0
4
A
d
r
.
=
0
0
0
0
D
0
1
=
2
1
3
2
4
1- Program address
2- Data Digit number
3- Value of the Data Digit
4- Control panel firmware revision
5.3 Entering a Value in a Program
Address
To enter a value in the program address:
1. Enter the program address.
2. Enter the value for each data digit and press [#] to
save the values.
The display shows the program address and displays
the value of each data digit after you enter it. The data
is programmed (saved) when you press the [#] key. The
control panel automatically increments to the next
program address.
To program the next address, enter the desired
information.
To read back the value of the address, press the [#]
key.
To program a different address, press the [*] key
two times and enter the program address.
If you make a mistake at any time, press the [*]
key twice before pressing the [#] key. This clears
the display and allows you to enter the desired
program address.
5.4 HEX Values
Some data digit values are greater than 9. These values
must be programmed by pressing the [*] key followed
by some other number. These values are displayed as
HEX characters (A to F) when entered. Example:
entering [*][0] at the keypad displays A.
The HEX character values are shown in Table 12.
Table 12: HEX Character Values
Keys Pressed HEX Character
[*][0] A
[*][1] B
[*][2] C
[*][3] D
[*][4] E
[*][5] F
5.5 Defaults
The DS7400XiV4 is shipped as a working, pre-
programmed control panel. Many of the programming
addresses might already be set to the values you need.
5.5.1 Defaulting the Control Panel
Entering [0][1][#] in Program Address 4058
immediately resets the control panel to the
factory default. Any programming already
done by the installer is erased. This action
cannot be reversed. Only enter [0][1][#] in
Program Address 4058 when you are
completely sure you want to erase all
installer programming.
To set the control panel’s programming values back to
the default:
1. Enter the programming mode.
2. Enter [4][0][5][8][0][1][#].
5.6 Exiting Programmer’s Mode
To exit Programmer’s Mode, press the [*] key for at
least 2 seconds. If no keypad entries are made for 4
minutes, the control panel automatically exits
Programmer’s Mode.