DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 38
Bosch Security Systems | 1/05| 4998154963B
5.9.5 Zone Bypass Programming: Program Addresses (2721 to 2724)
Zone bypass programming determines which zone functions can be bypassed. Zone functions that cannot be
bypassed cannot be force armed either. Fire zones can never be manually bypassed, but can be force armed. A
default of 0 or 8 means those zone functions can be bypassed.
This programming item does not affect Custom Arming Programming (Program Addresses 2725 to
2778) or Swinger Shunt Bypasses (see Section 5.8 General Control Panel Programming).
Zone Bypass Programming (Address 2721)
• Address: 2721
• Data Digit:
• Data Digit 1: ____ (see Table 27; default = 0)
• Data Digit 2: ____ (see Table 28; default = 8)
• Selections: 0 to 9, *0 to *5 (hexadecimal values that display as A through F at the keypads)
Table 27: Zone Bypass Programming (Address 2721, Data Digit 1)
Selections for Data Digit 1
Select Options 0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5
Zone Function 1 Can Be Bypassed
•
•
•
•
•
•
•
•
Zone Function 2 Can Be Bypassed
• •
• •
• •
• •
Zone Function 3 Can Be Bypassed
• • • •
• • • •
Zone Function 4 Can Be Bypassed
• • • •
• • • •
Table 28: Zone Bypass Programming (Address 2721, Data Digit 2)
Selections for Data Digit 2
Select Options 0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5
Zone Function 5 Can Be Bypassed
•
•
•
•
•
•
•
•
Zone Function 6 Can Be Bypassed
• •
• •
• •
• •
Zone Function 7 Can Be Bypassed
• • • •
• • • •
Zone Function 8 Can Be Bypassed
• • • •
• • • •