5.9.26 RS-232 Carriage Return/Line Feed Control
The RS-232 Carriage Return/Line Feed (CR/LF) Control allows you to choose between sending carriage
returns/line feeds or spaces to the DS7412 module. This is only used when Program Address 4019 Data Digit 2 is
programmed with the numbers 1 through 7 (see Section 5.9.24 RS-232 Interface Control Programming).
• Address: 4027
• Data Digit:
• Data Digit 1: ____ (see Table 87; default = 0)
• Data Digit 2: Must = 0
• Selections: 0 or 1
Table 87: Address 4027, Data Digit 1
Select Option Value
Send CR/LF
0
Send Spaces 1
5.9.27 Report Programming (Program Addresses 3207 to 3419)
• To send the User number along with open, close, or partial close reports: place an F (*5) in the extended digit.
• To disable a report (meaning that nothing is sent), place a ‘0’ in the reporting digit.
• When using SIA or Contact ID format, place a ‘1’ in the reporting digit of each report you enable. It is not
necessary to program the extended digit.
• For suggested values for 4/2, BFSK and Pager format, see Sections 12.1 to 12.3. For SIA and Contact ID, the
values sent are listed in Sections 13.1 and 13.2. For other formats, consult your central station.
• HEX values: Some Data Digit values are higher than 9. These values are programmed by pressing the [*] key
followed by another number. These values will display as HEX characters when entered. The HEX character
values are: *0 = A *1 = B *2 = C *3 = D *4 = E *5 = F
See Section 7.2.13 Report Programming for Report Programming glossary definitions.
Table 88: Report Programming (Addresses 3207 to 3419)
Report Address Default Reporting Digit 1 Reporting Digit 2
Keypad Fire Alarm 3207 00
Keypad Fire Restore 3208 00
Zone Funct. 1 Alarm 3209 10
Zone Funct. 2 Alarm 3210 20
Zone Funct. 3 Alarm 3211 30
Zone Funct. 4 Alarm 3212 40
Zone Funct. 5 Alarm 3213 50
Zone Funct. 6 Alarm 3214 60
Zone Funct. 7 Alarm 3215 70
Zone Funct. 8 Alarm 3216 80
Zone Funct. 9 Alarm 3217 00
Zone Funct. 10 Alarm 3218 00
Zone Funct. 11 Alarm 3219 00
Zone Funct. 12 Alarm 3220 00
Zone Funct. 13 Alarm 3221 00