DS7400XiV4-EXP | Reference Guide | 4.0 Operating Guide EN | 27
Bosch Security Systems | 1/05| 4998154963B
To perform a Fire Walk Test:
1. Press [PIN][#][9][1].
• Zone LEDs for any untested zones flash on
DS7445i/DS7445V2 keypads.
• The DS7447E/DS7447V2 displays “Fire
Test” followed by the zone number for any
zones not tested.
2. Pick any untested zone and manually cause a
detector to alarm using the method specified in the
detector’s installation instructions.
• The zone LED for the zone currently being
tested turns on steady on DS7445i/
DS7445V2 keypads.
• The DS7447E/DS7447V2 displays “Fire
Testing” followed by the zone number of
the zone currently being tested.
3. Clear the alarm condition from the detector using
the method specified in the detector’s installation
instructions, and trigger an alarm on the next
detector in that zone. Continue until all detectors in
that zone are tested.
• As each zone is tested, its zone LED turns
off on a DS7445i/DS7445V2 keypad.
• As each zone is tested, the
DS7447E/DS7447V2 display returns to
“Fire Test” and indicates the remaining
untested zones.
4. Test each zone as instructed by your installing
company.
5. Exit the Zone Test using [PIN][#].
A Fire Walk Test prevents the system from
sending any fire reports during the test.