DS7400XiV4-EXP | Reference Guide | 4.0 Operating Guide EN | 26
Bosch Security Systems | 1/05| 4998154963B
4.7 Testing Your System
4.7.1 Zone (System Walk) Test
The Zone Test is used to confirm that detectors report
alarms to the keypad. A Zone Test works on all zones,
except 24-hour zones and fire zones. While the keypad
is in a Zone Test, no control panel alarms activate an
alarm, except 24-hour zone alarms and fire alarms;
these override the Zone Test function.
To perform a Zone Test:
1. Press [PIN][#][8][1].
• The DS7445i/DS7445V2 zone LEDs of
any untested zones will flash.
• The DS7447E/DS7447V2 displays “Test
Zone” followed by the zone number of any
zones that have not been tested.
2. Pick any untested zone and manually cause a
detector to alarm using a method specified in the
detector’s installation instructions.
• The DS7445i/DS7445V2 zone LED for the
zone currently being tested will turn on
steady.
• The DS7447E/DS7447V2 displays “Now
Testing” followed by the zone number of
the zone that is currently being tested.
3. Clear the alarm condition from the detector using a
method specified in the detector’s installation
instructions, and trigger an alarm on the next
detector in that zone. Continue until all detector's
in that zone are tested.
• As each zone is tested, its
DS7445i/DS7445V2 zone LED turns off.
• As each zone is tested, the
DS7447E/DS7447V2 display returns to
“Test Zone” and indicates the remaining
untested zones.
4. Test each zone.
5. Exit the Zone Test using [PIN][#].
4.7.2 Battery Tests
You can test the battery and the local sounder, or just
test the battery. If these tests are performed from a
Master keypad, it must be in Single Partition Mode.
System Tests are not available from RF (wireless)
keypads.
To start a Local Battery/Sounder Test:
Press [PIN][#][8][5].
All keypad LEDs turn on. The keypad sounder and all
alarm sounding devices operate for two seconds. If the
test fails, the control panel indicates a control problem.
See Section 4.6 Keypad Error Displays.
To start a Battery Test:
• Press [PIN][System Reset]. The control panel
performs a battery test. The control panel reports a
Low Battery or a Low Battery Restoral if
necessary.
4.7.3 Communication Test
This test is available only if the system transmits
alarms and system information to a monitoring service,
and is programmed by the security installing company
to permit control panel tests. This test can be
performed from a Master Keypad. The account code
for area #1 is sent with the test report. System Tests
are not available from RF (wireless) keypads.
To initiate a Communication Test:
Press [PIN][#][8][2].
A long beep sounds. A test report is sent to the
monitoring service. If the test fails, the keypad sounds
continuously. Press [System Reset] to silence the
sounder.
This test might take several minutes to
complete.
4.7.4 Fire Walk Test
This test is used to confirm that smoke detectors report
alarms to the keypads. The Fire Walk Test tests all fire
zones, including verified fire and waterflow.
At the start of the Fire Walk Test, a Fire Walk Test
report, if programmed, is sent to the central station.
Fire alarm reports are not sent to the central station
during the Fire Walk Test. A Fire Walk Test restoral is
sent upon completion of the Fire Walk Test.
The Fire Walk Test runs for 20 minutes after it is
started. The test time is extended to 20 minutes every
time another zone is tested.
When a fire zone is tested, any output programmed to
follow that zone activates for 5 seconds.