DS7400XiV4-EXP | Reference Guide | 2.0 Specifications EN | 11
Bosch Security Systems | 1/05| 4998154963B
Table 4: Backup Battery Calculation (continued)
Device Quantity Standby Current
per Device
Total Standby
Current
(Quantity x Standby
Current per Device)
Alarm Current
per Device
Total Alarm Current
(Quantity x Alarm
Current per Device)
MX250 Series
Multiplex Smoke
Detectors
500 µA 560 µA
MX775i PIR Detector 200 µA 200 µA
MX794i PIR Detector 800 µA 800 µA
MX934i PIR Detector 200 µA 200 µA
MX938i PIR Detector 200 µA 200 µA
RF3222/RF3222E
Wireless Receivers
30 mA 30 mA
2-Wire Smoke
Detectors
4-Wire Smoke
Detectors
Bells, Horns, and so
on
Other Sensors
Door Access Control
Module (DACM)
Other
Grand Total Grand Total
1
= Maximum current draw if using the control panel power supply. Total of all outputs cannot exceed 750 mA.
2
= When calculating Standby and Alarm Current for the Octal Relay Module, use 10 mA plus 40 mA for each activated
relay.
3
= 84 mA max, 80 mA nominal 10 Base-T; 110 mA max, 100 mA nominal 100 Base-T
Table 5: Standby Current Load
Rechargeable
Battery Size
Maximum
Standby for
4 hours
Maximum
Standby for
8 hours
Maximum
Standby for
24 hours
Maximum
Standby for
48 hours
Maximum
Standby for
60 hours
Maximum
Standby for
72 hours
Maximum
Standby for
80 hours
7 Ah 1.0 A 470 mA - - - - -
8 Ah 1.2 A 580 mA - - - - -
14 Ah 1.5 A 1.1 A 270 mA - - - -
15 Ah 1.5 A 1.2 A 300 mA - - - -
17.2 Ah 1.5 A 1.5 A 380 mA 100 mA - - -
21 Ah 1.5 A 1.5 A 500 mA 160 mA 100 mA - -
28 Ah 1.5 A 1.5 A 740 mA 280 mA 190 mA 130 mA 100 mA
30 Ah 1.5 A 1.5 A 800 mA 310 mA 210 mA 150 mA 120 mA
35 Ah 1.5 A 1.5 A 970 mA 400 mA 280 mA 200 mA 170 mA