Bosch DS7400XiV4-EXP Spécifications Page 102

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 144
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 101
DS7400XiV4-EXP | Reference Guide | 6. Troubleshooting Guide EN | 102
Bosch Security Systems | 1/05| 4998154963B
Table 136: Reporting Troubleshooting (continued)
Symptom Probable Cause Possible Solutions
Control panel never sends history to
RPS.
a. Not programmed to send history.
b. Time and date not set.
a. Check programming.
b. Verify that the time in the control
panel is set.
The control panel test report is not
being sent.
a. Report not programmed properly.
b. There was a control panel problem
at the time the report should have
been sent. If this is the case, the
control panel test report is not
sent. Instead, the control panel
sends the "System Off Normal"
report.
a. Check programming addresses
4022, 4023, 4026, and 3340.
b. Program "System Off Normal"
report in address 3347.
6.3 Zone Problems
Table 137: Zone Troubleshooting
Symptom Probable Cause Possible Solutions
Fire Alarm displays on keypad but no
zone numbers are displayed.
In Commercial Fire Mode, fire alarms
must be silenced before the zone
number appears.
Enter a valid disarm PIN and press #,
then enter a valid disarm PIN and press
# again to display the zones.
Every other zone displays Not Ready.
Zone Programming is incorrect. Program as a multiple zone input for
DS7432E or DS7460, a single zone
input for contacts and sensors, or
program as a DS7465i.
Vue de la page 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 143 144

Commentaires sur ces manuels

Pas de commentaire