
DS7400XiV4-EXP | Reference Guide | 3.0 Control Panel Installation EN | 16
Bosch Security Systems | 1/05| 4998154963B
3.5 Telephone Connections
Use the following steps to make the telephone
connections to the control panel:
1. To prevent jamming of signals, wire the RJ31X jack
or RJ38X jack to support line seizure as shown in
Figure 5.
2. Install the jack on the street side of the phone
switch, wired ahead of any PBX equipment. Line
seizure temporarily interrupts normal phone usage
while the control panel transmits data.
3. Confirm that the control panel seizes the line,
acquires dial tone, reports correctly to the receiver,
and releases the phone line to the in-house phone
system.
4. Connect the telephone cord’s flying leads to the
telephone terminals as shown in Figure 6 (Red to A;
Gray to A1; Brown to B1; Green to B).
5. Plug the other end of the cord to the RJ31X jack or
RJ38X jack.
Figure 5: RJ31X/RJ38X Wiring
1 2 3 4 5 6 7 8
TH RHT R
3
4
5
6
1 2 3 6 7 84 5
T
R
TH
RH
1
2
1- Outside Telco (PSTN)
2- Premises telephone
3- RJ31X or RJ38X jack
4- Telco connector block
5- Phone line connections to control panel
6- Bar short removed on Telco connector block
insertion – positions 1 & 4 and 5 & 8
3.6 Keypad Wiring
Consult your keypad’s installation manual for complete
installation instructions. Connect the keypads to the
keypad bus or option bus terminals as shown in Figure
6.
Keypads contain static-sensitive
components. Follow anti-static procedures
when handling the keypads.
Shared cable is not recommended for
keypad, multiplex, options bus, telephone,
or siren wiring.
Figure 6: Phone Line and Keypad Bus Terminal
Connections
9
1
0
11
1
2
1
3
1
4
1
5
1
6
R
B
G
Y
G
B
S
R
T
T
H
R
H
R
1
3
2
3
1- Keypad bus—You can use up to 15 keypads.
Can be “home run” or “daisy-chained.”
Maximum wire length for each is 305 m
(1000 ft). Maximum total wire length in system
is 1830 m (6000 ft) when using 0.8 mm (#22
AWG) or 1.0 mm (#18 AWG) cable.
2- Phone line
3- Keypad. Keypads 1 to 10 connect to the
keypad bus, and Keypads 11 to 15 connect to
the option bus. See Section 3.9 Option Bus
Wiring.
3.7 Zones 1 to 8 Wiring
Zones 1 to 8 are intended for connection of Normally
Open or Normally Closed alarm contacts. They can
also be used for compatible 2-wire smoke detectors.
These zones require a 2.21 kΩ resistor (P/N 25899) at
the end of the loop. Power is momentarily removed
from L+ after a [PIN][System Reset] or during a fire
verification. See Figure 7 terminals 19 through 30, and
see Figure 8.
Zones 1 to 8 assignments are programmed in Address
0031 to 0038. See Section 5.9.2 Zone Programming:
Assigning a Zone Function to the Zone.
Commentaires sur ces manuels