DS7400XiV4-EXP | Reference Guide | 6. Troubleshooting Guide EN | 106
Bosch Security Systems | 1/05| 4998154963B
Table 138: General System Troubleshooting (continued)
Symptom Probable Cause Possible Solutions
#87 display = Ground Fault
#89 display = System Fault 04
There is a short to ground somewhere
in the system.
Disconnect field wiring from each
terminal while watching the keypad
display. When the keypad power LED
stops flashing, you have found the wire
that is causing the ground fault.
The LED does not stop
flashing if there is another
system fault present.
If there is no keypad nearby, or another
control problem exists, you can use a
volt meter to find the ground fault:
a. Connect the negative lead of a
volt-meter to the control panel
ground terminal.
b. Connect the positive terminal to
the Aux Power - terminal.
You should read -4.5 to -7.5 VDC. A
reading considerably higher or lower
indicates a ground fault.
Disconnect field wiring from each
terminal while watching the meter.
When the voltage reading returns to
between -4.5 and -7.5 VDC, you have
found the wire that is causing the
ground fault.
#87 display = AR IB Queue Full
#89 display = System Fault 51
The message queue in the RF modem
is full and no messages can get out to
the radio network.
Check RF coverage of the unit and
check for RF noisy environment.
#87 display = AR Host Down
#89 display = System Fault 52
The central station receiver is no longer
available to the network.
Contract the central station and notify
of status.
#87 display = AR Unreg. Modem
#89 display = System Fault 53
The modem is not registered through all
parts of the network.
Contact the network administrators or
technical service.
#87 display = AR Power Fail
#89 display = System Fault 54
There is a possible problem with the
DS7416i Module.
Return for service.
#87 display = AR Network Lost
#89 display = System Fault 55
The DS7416i Module has lost contact
with the radio network.
Check the location and coverage of the
unit.
#87 display = AR Modem HW Err
#89 display = System Fault 56
There is a possible problem with the
radio modem.
Replace the unit.
#87 display = AR Modem SW Err
#89 display = System Fault 57
The DS7416i Module is having trouble
communicating with the radio modem.
Check for noisy environment and
replace the unit if the problem
continues.
#87 display = AR Opt. Bus Err
#89 display = System Fault 58
The control panel can no longer
communicate with the DS7416i
Module.
Check the wiring between the
DS7400Xi and the DS7416i Module.
#87 display = AR Corrupt MSG
#89 display = System Fault 59
Communication between the control
panel and the DS7416i Module is
corrupted.
Check for noisy environment, and
check the wiring between the
DS7400Xi and the DS7416i Module.