DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 31
Bosch Security Systems | 1/05| 4998154963B
5.9 Programming a Zone
Programming a zone is a four step process. Perform the following steps, in this sequence, to program a zone:
1. Program zone functions (what the zone does in alarm). See Section 5.9.1 Zone Function Programming.
2. Assign a zone function to the zone. See Section 5.9.2 Zone Programming: Assigning a Zone Function to the Zone.
3. Assign a zone type to the zone. See Section 5.9.3 Zone Programming: Zone Type Program Addresses.
4. Assign the zone to an area. See Section 5.9.4 Zone Partition Assignment.
Step 1: Programming Zone Functions
5.9.1 Zone Function Programming
A zone function describes how a zone behaves. Up to 30 different zone functions can be programmed. You may
use the default values and skip this step, or change the defaults, or add new zone functions. See Section 7.2.2 Zone
Function Programming for zone function programming glossary definitions.
See the DX7400Xi-EXP Wireless Reference Guide (P/N: 4998154790) for additional information.
Address: 0001 to 0030
Data Digit:
Data Digit 1: ____ (see Table 17; see Table 20 for defaults)
Data Digit 2: ____ (see Table 18; see Table 20 for defaults)
Selections: 0 to 7, *2 to *5 (hexadecimal values that display as C through F at the keypads)
Table 17: Zone Function Programming (Address 0001 to 0030, Data Digit 1)
Selections for Data Digit 1
Select Options 0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5
Invisible Alarm
Silent Alarm
Steady Alarm Output
Pulsing Alarm Output
Alarm on Short
Alarm on Open
Trouble on Open
1
Trouble on Short
Table 18: Zone Function Programming (Address 0001 to 0030, Data Digit 2)
Select Options Value Select Options Value
Interior Delayed 0 Day Monitor 8
Perimeter Instant 1
Keyswitch
2
9
24-Hour 2 Fire Zone with Verification *0
Entry/Exit Delay #1 3 Fire Zone without Verification *1
Entry/Exit Delay #2 4 Waterflow *2
Interior Entry/Exit Follower 5 Supervisory *3
Interior Home/Away 6 Entry/Exit Delay Cancel 1 *4
Interior Instant 7 Entry/Exit Delay Cancel 2 *5
1
Only when disarmed. When armed, this becomes Alarm on Open or Short for non-24-hour zones.
2
If Data Digit 2 = 9 (keyswitch), see Table 19 to determine the value for Data Digit 1.