DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 52
Bosch Security Systems | 1/05| 4998154963B
Regardless of Which Commercial Fire Mode is Chosen
Regardless of which Commercial Fire Mode is chosen, the following parameters are forced when exiting Local
Programmer’s Mode:
• Zone Function 12, Address 0012, is 7 *0. (Alarm on Short, Trouble on Open, Pulsing Fire with verification)
• Zone Function 13, Address 0013, is 7 *1. (Alarm on Short, Trouble on Open, Pulsing Fire without verification)
• Zone Function 14, Address 0014, is 7 *2. (Alarm on Short, Trouble on Open, Pulsing Water Flow)
• Zone Function 15, Address 0015, is 7 *3. (Alarm on Short, Trouble on Open, Pulsing Supervisory)
• Zone Bypass Address 2722 does not allow Zone Functions 12 - 15 to be bypassed.
• Emergency Key, Address 3147, Data Digit 1, becomes a 3 if programmed previously as a 2. Data Digit 2
becomes a 2 if programmed previously as a 3.
• Panic Key, Address 3148, Data Digit 1, becomes a 2 if programmed previously as a 3.
• Fire Bell Cutoff, Address 4032: If less than 5, set to 5, otherwise untouched.
• The AC Fail Report delay is randomly between 6 to 12 hours regardless of the delay time programmed in
4034. Also, the AC Fail Report is not sent as a “tag-along.”