
20 ms Option Loop Response Time
(sec)
150 ms Option Loop Response Time
(sec)
6 10 14 120
7 15 15 200
For zone pulse count time, options 0 to 7 have a zone loop response time of 20 ms and
options 8 to 15 have a zone loop response time of 150 ms. Loop response time is the length of
time a zone must be unsealed before it can register as a valid pulse.
Inertia sensors should use options 0 to 7 and PIR detectors should use options 8 to 15.
Notice!
24-Hour Zones cannot receive any handover pulses from other zones. 24-Hour Zones can hand
over pulses to other zones.
Zone Options 1
This location has four programming options. You can select any combination of the options by
programming a single value. Calculate this value by adding the option bit numbers together.
Option Description
1 Lockout Siren/Lockout Report
2 Delay Alarm reporting
4 Silent Alarm
8 Sensor Watch
1 – Lockout Siren and Lockout Report
Lockout refers to one activation per arming cycle (that is, a zone programmed for Lockout can
activate the sirens or communication module only once).
The next time the system is armed, the zone can activate the sirens and report once more.
Restore signals are sent when the system is disarmed.
Lockout Siren and Lockout Report are separate for each zone. If a zone's siren or report is
locked out, the other zone's siren or report still can be activated.
Use Location 379 to set the number of times the siren is allowed to activate before it is locked
out. Use Location 380 to set the number of times the communication module is activated
before lockout takes effect.
When a zone is activated before Siren Running Time (Location 479) is expired, if any other
zone is activated, its Swinger Shutdown Count for Siren and Swinger Shutdown Count for
Report will not increase 1. If any other zone is activated, its Swinger Shutdown Count for
Siren and Swinger Shutdown Count for Report will increase 1 only after Siren Running Time
(Location 479) is expired,.
2 – Delay Alarm Reporting
Select this option to allow the reporting of alarms on selected zones to be delayed so that a
user can enter a code to cancel alarms that are not required to report. All sounding devices
(horn speaker, strobe, and bell outputs) operate as soon as the alarm occurs, but the
communication module does not operate until the delay time programmed in Locations 474
and 475 expires.
4 – Silent Alarm
9.3.5
Control Panel Zone Information | en 93
Installation Guide 2014.07 | 00n | F01U298026
Commentaires sur ces manuels