By default, the control panel waits approximately 30 sec for receipt of a valid handshake tone
after it dials the monitoring station. The handshake tone indicates to the control panel that it
reached the monitoring station and can now transmit its messages. Selecting this option
extends this wait time from 30 sec to 60 sec.
Item Location Default
Communicator Options 2 178 0
Value Description
1 Arm/Disarm reports only if previous alarm
2 Arm/Disarm reports for STAY Mode 1 and STAY Mode 2
4 Delay siren until transmission complete
8 Extend time to wait for handshake from 30 to 60 sec
Communicator Options 3
1 – Set DTMF Dialing Pulses to 1 Digit/Sec
If this option is not selected, the DTMF dialing format dials at 5 digits per sec (that is, 100 ms
tone, 100 ms pause, 100 ms tone, 100 ms pause).
If this option is selected, the DTMF dialing format dials at the rate of 1 digit per sec (that is,
500 ms tone, 500 ms pause).
2 – Lockout Telephone Line Fail Alarm
Selecting this option allows an audible alarm only once per arming cycle when the control
panel detects the telephone line is cut or disconnected. This option does not follow the
Swinger Shutdown Count for Siren, in which you can program the number of times a zone can
sound an alarm during an arming cycle. Use Location 176 to program the telephone line fault
options.
Item
Location Default
Communicator Options 3 179 2
Value Description
1 Set DTMF dialing pulses to 1 digit/sec
2 Lockout telephone line fail alarm
4 Reserved
8 Reserved
A-Link Options
The following A-Link options are available only for link through the telephone line. The options
are not related to connection through network.
1 – Enable Upload/Download Using A-Link
Select this option to use the A-Link Plus software to program the control panel remotely. The
control panel does not respond to A-Link if this option is not selected.
13.12
13.13
Control Panel Communicator Information | en 121
Installation Guide 2014.07 | 00n | F01U298026