Select this option to force the control panel to send a Test Report after the siren is reset. This
can be used to indicate to the monitoring station that the control panel itself was not
tampered with during the alarm period.
4 – Auto Arm in STAY Mode 1
Select this option if automatic arming in STAY Mode1 is preferred to automatic arming in
AWAY Mode.
Program the time that the control panel automatically arms itself in Locations 482 to 485. Set
the Auto Arming Pre-Alert Time in Location 481
For partitioned control panels, both areas are automatically armed.
8 – STAY Indicator To Display Day Alarm Status
If this option is selected, the STAY indicator flashes once every 3 sec when Day Alarm is
enabled.
Specify Day Alarm zones in Location 265.
You can turn Day Alarm on and off by holding down [4] for 2 sec. Three beeps indicate Day
Alarm is turned on and two beeps indicate Day Alarm is turned off.
Consumer Options 2
Item Location Option Default New
Consumer Options 2 0497 1 = Codepad displays extinguish after 60 sec.
2 = Single button arming allowed (AWAY/STAY
Modes 1 and 2)
4 = Single button disarming allowed (STAY
Modes 1 and 2)
8 = Alarm memory reset on disarm
2
1 – Codepad Display Extinguish after 60 Sec
If this option is selected, all indicators on the remote codepad display are extinguished if a
button is not pressed for 60 sec. The indicators lights again when there is an alarm (except a
silent alarm), when a button is pressed on the codepad, when the AC MAINS fail beeps, or if
the Entry Timer is activated.
2 – Single Button Arming Allowed
If this option is selected, the hold-down functions for arming in AWAY Mode, STAY Mode 1 and
STAY Mode 2 are functional.
4 – Single Button Disarming Allowed
This option operates only when Option 2 in this location is also selected. This option allows
hold-down functions for disarming from STAY Mode 1 and STAY Mode 2.
8 – Alarm Memory Reset on Disarm
If this option is selected, the alarm events memory clears from the remote codepad when the
system is disarmed. If this option is not selected, the system must be armed and disarmed
again to clear alarm memory from the remote codepad.
11.6
Control Panel System and Consumer Options | en 109
Installation Guide 2014.07 | 00n | F01U298026