Primary Telephone Number for Receiver 1 and Receiver 2
When the control panel transmits a report, the panel dials the Primary Telephone Number to
contact the monitoring station, for example. If the call is successful, the relevant information
is transmitted and the communicator returns to Standby Mode.
If unsuccessful, the communicator attempts two more calls using the Primary Telephone
Number for Receiver 1. If these calls are unsuccessful, the communication module calls the
Secondary Telephone Number for Receiver 1 up to three times. If the dialing sequence is still
unsuccessful, the control panel repeats this sequence by dialing the Primary and Secondary
Telephone Numbers for Receiver 2 (if they are programmed).
If the first six attempts are unsuccessful and no telephone numbers for Receiver 2 are
programmed, this procedure is repeated every 10 min continuously.
Contact your monitoring station for the correct telephone numbers before you program these
locations. With a text codepad, go to menu 711 First Phone Number to program the primary
telephone numbers.
Item
Location Default
Phone Number 1 – Receiver 1 0000 – 0015 15
Phone Number 1 – Receiver 2 0040 – 0055 15
Secondary Telephone Number for Receiver 1 and Receiver 2
For programming information, refer to Primary Telephone Number for Receiver 1 and Receiver 2,
page 115. With a text codepad, you go to menu 712 Second Phone Number to program the
secondary telephone numbers.
Item Location Default
Phone Number 2 – Receiver 1 0016 – 0031 15
Phone Number 2 – Receiver 2 0056 – 0071 15
Transmission Format for Receiver 1 and Receiver 2
Select the desired transmission format here. These locations select the data format used to
transmit to the base station receiver. Location 33 selects the data format used to transmit to
the base station receiver 1. Location 73 selects the data format used to transmit to the base
station receiver for receiver 2. These locations also allow you to configure the control panel
for domestic formats.
With a text codepad, go to menu 713 Transmit Format to set the transmission for Receiver 1
and Receiver 2.
value 0 - Not used
value 1 - contact ID (default)
value 4 - Domestic
value 6 - SIA fast
value 7 - SIA Slow
value 8 - CSVIP
value 9 - Email