Example
If Area 1 is armed in AWAY Mode or STAY Mode1 or STAY Mode 2, Output Event Type 5,6
operates. The output is reset when Area 1 is disarmed.
5,10 Area 1 Is Disarmed
5,11 Area 2 Is Disarmed
These two outputs operate when their corresponding area is disarmed. The output is reset
when the corresponding area is armed.
Example
If Area 1 is disarmed, Output Event Type 5,10 operates. The output is reset when Area 1 is
disarmed.
5,14 Any Areas Armed
This output operates when either Area 1 or Area 2 is armed in AWAY Mode or STAY Mode 1.
The output is reset when both areas are disarmed.
5,15 Any Areas Disarmed
This output operates when either Area 1 or Area 2 is disarmed. The output is reset when both
areas are armed in AWAY Mode or STAY Mode 1 or STAY Mode 2.
6,2 Remote Control 4
6,3 Remote Control 5
6,4 Remote Control 6
6,5 Remote Control 7
6,6 Remote Control 8
6,7 Remote Control 9
6,8 Remote Control 10
6,9 Remote Control 11
6,10 Remote Control 12
These outputs operate output when using the master code function or A-Link software or
Smartphone App (RSC) to turn remote output on. The output is reset when using the master
code function or A-Link software or Smartphone App (RSC) to manually turn remote output off
or automatically turn remote output 3 off when the ON time expires if output polarity is from 3
to 6 or from 10 to 13.
Output Polarity
There are fifteen different polarities. Each polarity is designated by a number that you program
into the appropriate location for the output.
0 – Output Not Used
If an output is not required, program the polarity as 0.
1 – Normally Open, Going Low
This polarity is normally open circuit and switches to 0 V when the event occurs. The output
switches back to open circuit when the event is restored. Time parameters do not apply to
this polarity.
2 – Normally Open, Pulsing Low
This polarity is normally open circuit and switches to pulsing 0 V when the event occurs. The
output switches back to open circuit when the event is restored. Time parameters vary the On
time (Time base) and Off time (Time Base*Time Base Multiplier) of the pulse.
3 – Normally Open, One-Shot Low
This one-shot polarity is normally open circuit and switches to 0 V when the event occurs. The
output switches back to open circuit when the time parameter setting expires. This one-shot
time setting always runs its full duration and cannot be manually reset.