1 – Codepad Panic to Be Silent
If this option is selected, a Codepad Panic Alarm or Radio Remote Panic Alarm does not
operate the horn speaker, the bell, or the strobe outputs. If this option is not selected, all
three outputs operate after a Codepad Panic Alarm is activated when a user presses [1] and
[3] or [STAY] and [AWAY] at the same time on the remote codepad. Selecting this option does
not affect the operation of the communication report.
2 – Codepad Fire to Be Silent
If this option is selected, a Codepad Fire Alarm does not operate the horn speaker, the bell, or
the strobe outputs. If this option is not selected, all three outputs operate after a Codepad
Fire Alarm is activated when a user presses [4] and [6] at the same time on the remote
codepad. Selecting this option does not affect the operation of the communication report.
4 – Codepad Medical to Be Silent
If this option is selected, a Codepad Medical Alarm does not operate the horn speaker, the
bell, or the strobe outputs. If this option is not selected, all three outputs operate after a
Codepad Medical Alarm is activated when a user presses [7] and [9] at the same time on the
remote codepad. Selecting this option does not affect the operation of the communication
report.
8 – Access Denied (Code Retries) to Be Silent
If this option is selected, a Codepad PIN Error Alarm does not operate the horn speaker, bell,
or the strobe outputs. If this option is not selected, all three outputs operate after a Codepad
PIN Error Alarm occurs. Selecting this option does not affect the operation of the
communication report.
System Options 3
Item Location Option Default New
System Options 3 0494 1 = AC fail after 1 hr. (Disabled = after 2 min.)
2 = Ignore AC fail
4 = Pulse count handover allowed
8 = Handover delay to be sequential
8
1 – AC Fail after 1 Hour
If this option is selected, the MAINS indicator flashes when the AC MAINS supply is
disconnected. An AC Loss signal (Contact ID Event Code 301) is transmitted to the base
station receiver after the AC MAINS supply is disconnected continuously for longer than 60
min.
If this option is not selected, the MAINS indicator flashes and an AC Loss signal (Contact ID
Event Code 301) is transmitted to the base station receiver after the AC MAINS power is
disconnected continuously for 2 min.
The MAINS indicator stops flashing when the AC MAINS supply is restored longer than 2 min.
An AC Loss Restore Report is transmitted to the base station receiver after the AC MAINS
supply is restored continuously for more than 2 min regardless of whether this option is
selected.
2 – Ignore AC Fail
If this option is selected, the MAINS indicator does not flash and the codepad does not beep
every minute when the AC MAINS is disconnected from the control panel. If you want a
programmable output to operate when the AC MAINS fails, use Output Event Type 1,4 AC Fail.
4 – Zone Pulse Count Handover
11.3
Control Panel System and Consumer Options | en 107
Installation Guide 2014.07 | 00n | F01U298026