Solution 16 i
32
Bosch Security Systems 09/07 BLCC500R FTR1.02
Quick Start Guide
Copyright © 2007 E&OE
Inputs > Tamper Inputs >
Tamper Options MENU 3-6-0
1 Display Panel Tamper Y
2 Report Panel Tamper Y
3 Audible Panel Tamper Y
4 Display Expander Tamper Y
5 Report Expander Tamper Y
6 Audible Expander Tamper Y
7 Reserved N
8 Reserved N
This location is a Bit option field. Press Keys [1] – [8] to turn ON and
OFF the required options. The option is selected or ON when the
coresponding zone indicator is on. Press [OK] To Save when finished.
Inputs > Input Testing >
Walk Test All Zones
MENU 3-9-0
Walk Test A Zones
MENU 3-9-1
Inputs > Input Testing >
Sensor Watch Time
MENU 3-9-2
0 3 0
(*** System Wide Parameter ***)
DAYS
Enter 0 – 255 + [OK] To Program The Sensor Watch Time In Days
(0 = Disabled)
Ou tpu t Progra mmi ng
Outputs > Commands >
Output Status
MENU 4-0-0
Turn Output On/Off
MENU 4-0-1
Outputs > Properties >
Output Name
MENU 4-1-0
O u t p u t 1 N a m e
Use [] and [] Keys To Scroll the Cursor Left and Right. Use Keys [0]
– [9] + [] and [] To Select Characters. When finished press [OK] To
Save. Press [OFF] To Clear From The Current Cursor Position.
Outputs > Properties >
Event Type
MENU 4-1-1
0 0 0
Enter desired Event type 0 – 255 + [OK].
See Output Event Type table for available options.
Outputs > Properties >
Event Assignment
MENU 4-1-2
0 0 1
Enter 0 to 255 to program the Area, User, Zone, Keypad or Access
Group Number You Want The Output To Follow Then Press [OK].
(0 = Unrestricted all Areas, Users, Zones etc)
Ou tpu t D efa ult Table
The table below list the default values for all Output parameters in the Solution 16i. Outputs 1 to 4 are High current
digital outputs. Outputs 5 to 8 are only available if the optional Output Relay Expander Boards (CM710B) are fitted.
Options marked N/A = Not Applicable.
Programming Option Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8
Output Name
External
Siren
Strobe
Light
Smoke
Sensor PWR
Internal
Siren
Output 5
Name
Output 6
Name
Output 7
Name
Output 8
Name
Event Type
36
(External
Siren)
48
(Strobe)
49
(Smoke
Sensor GND)
37
(Internal
Siren)
0 0 0 0
Event Assignment
1 1 1 1 1 1 1 1
Output Polarity
14 6 11 6 0 0 0 0
Time Parameter
N° Of Hours
000 008 000 000 000 000 000 000
N° Of Minutes
005 000 000 005 000 000 000 000
N° Of Seconds
000 000 010 000 000 000 000 000
N° Of 1/10 Seconds
000 000 000 000 000 000 000 000
Output Options
Do not Operate If Low Battery
Y Y Y Y N N N N
Display Output Overload
Y Y Y Y N/A N/A N/A N/A
Report Output Overload
Y Y Y Y N/A N/A N/A N/A
Display Missing Output
Device
Y N N N N/A N/A N/A N/A
Report Missing Output Device
Y N N N N/A N/A N/A N/A
Alarm On Device Fail
N N N N N/A N/A N/A N/A
Block Output If Armed All On
N N N N N N N N
Display Status On Keypad
N N N N N N N N
Table 20: Output Default Table