19
Bosch Security Systems 09/07 BLCC500R FTR1.02
Solution 16 i
Quick Start Guide
Copyright © 2007 E&OE
Enteri ng Programm ing Mode
To enter installer program mode enter, PIN + [MENU].
The default Installer PIN is 1234.
The default Master Code PIN is 2580.
The Red and Green LED indicators on the keypad will flash
to confirm Installer programming mode is active.
i
Note
All areas must be disarmed with no active alarms.
To disarm all areas enter the Installer PIN and hold
the [OFF] Key for 2 seconds.
Exiting Pro gram min g M o de
Press and hold down [MENU] key for 2 seconds.
i
Note
You can also select End from the menu and press
[OK] to exit.
Progra mmi ng Str ucture
The ICON system utilises a mixture of text menus and
location numbers to simplify programming for both end
users and installers.
All programming options can be accessed by entering the
appropriate location or menu number followed by the
[OK] key, however only a limited number of text menus
are provided. As the installer you have access to both
programming methods.
Most end user functions can be accessed via the text menu
which simplifys operation and reduces training time.
1) Enter Program Mode. [1234 + MENU]
2) Enter the desired location number to program and
press [OK]. Follow the prompts.
3) Alternatively, press [MENU] and use the arrow and
OK keys to navigate through the text menus.
4) At any time you are free to enter the location you
wish to move to followed by the [OK] key.
5) To exit programming navigate to the end option
and press [OK], alternativly hold the [MENU] key
down for 2 seconds.
Key Description
Scrolls Cursor Left
Scrolls Cursor Right
Scrolls Cursor Up
Scrolls Cursor Down
OK Enter Menu Options or Saves Changes
MENU
Go Back One Level, Hold Down to Exit
Programming Mode, Abort Changes
0 to 9 Enter Data Value, Toggle Bit Option
ON Turn On Functions, Accept Data
OFF Turn Off Functions, Clear to End of Line
Table 11: Keys Used During Programming
Inte rpret ing The Text Dis play
The ICON keypad text display includes space for up to
6 characters to be displayed at one time. To simplify
programming, some text menus have been abbreviated.
The following table list the upper case, numbers and some
of the special characters which can be displayed on the
keypad. See the Character Set Table at the end of this
document for a complete character listing.

Figure 24: Text Characters Which Can Be Displayed.
Progra mmi ng BIT Op tio ns
The ICON system includes a number programming locations
which are know as option bit locations. Each of these has
up to 8 different parameters which can be selected.
To program BIT locations, enter the location number
followed by the [OK] key. The system will then display the
currently selected options in that location.
The numbers 1 to 8 are used to represent the options state.
For example if the number is ON then the coresponding
option is enabled, if the number is OFF then the option is
disabled.
To toggle the option state, simply press the number on the
keypad coresponding to the option.
When finished press the [OK] key to save any changes.
You should refer to the IRG or Installation manual for
detailled explanation of the various options.