ALARMS
6 720 806 768 (2013/02)58
>> Alarm indication room sensor (room controller)
>>> Block alarm indicator lamp
Set if the indicator lamp should be off or not.
The setting applies to all room controllers.
>> General alarm level
>>> Alarms and warnings
No means that alarms produce a signal on the general alarm output. Yes
means that alarms as well as warnings produce a signal on the general
alarm output.
20.12 ACCESS LEVEL
Access level is Customer as standard: This level gives you access to all
functions that the user requires. The installer also has access to the
additional functions required at installation.
20.13 RETURN TO FACTORY SETTINGS
▶Select Return to factory settings and Yes to reset all settings to the
factory settings. Settings made by the customer are not affected.
21 ALARMS
21.1 SOFT STARTER
The soft starter has four different alarm causes, see table below.
Type 2 alarms are due to large voltage variations in the electricity grid.
Type 3 alarms indicate the existence of a fault in the compressor.
Types 4 and 5 alarms are there to protect the soft starter.
21.2 ALARMS
This section includes:
Information log ( Chapter 20.11)
Delete information log ( Chapter 20.11)
Alarm log ( Chapter 20.11)
Delete alarm log ( Chapter 20.11)
Alarm history ( Chapter 20.11).
21.3 CONTROL UNIT AND ROOM CONTROLLER ALARM
LAMP
The status lamp on the control unit is used to show ON/OFF status for the
heat pump but also to show possible alarms. The status lamp is therefore
also called alarm lamp.
The room controller alarm lamp can be blocked.
The room controller display is used to indicate alarms for some alarm
categories ( 21.8). The display window slowly flashes red until the
alarm has been acknowledged in the heat pump control unit, or been
automatically reset.
The room controller alarm display function is referred to as an alarm
lamp in this chapter.
The room controller alarm lamp can be blocked.
21.4 ALARM DISPLAY
When an alarm/warning occurs, the display shows information about
what has happened. At the same time, information is saved in the alarm
log and alarm history.
21.5 ALARM BUZZER AT ALARM
At an alarm the alarm buzzer on the heat pump sounds for one second
per alarm buzzer interval set. At certain times of the day the alarm buzzer
can be blocked or blocked altogether.
In the event of a warning, the alarm buzzer does not sound.
21.6 ACKNOWLEDGEMENT OF ALARMS
Acknowledgement means that you have to press to make the
alarm window disappear. What happens after acknowledgement is
described in the respective alarm description.
In most cases, warnings do not have to be acknowledged. The alarm
window disappears by itself once the warning cause has disappeared. It
is, however, possible to acknowledge the warning.
21.7 ALARM TIMER, ALARM MODE
In the event of an alarm that stops the compressor the control unit starts
a timer at 1h. If the fault does not recur additional heat may start when
the timer has counted down.
Factory setting Yes
Alternative No/Yes
Table 167 Block indicator lamp
Factory setting No
Alternative No/Yes
Table 168 Alarms and warnings
Factory setting No
Alternative Yes/No
Table 169 Return to factory settings
The soft starter has normally 1 minute restart delay. The
restart delay is 5 minutes at an alarm.
Soft starter fault indicators are located on the soft starter
unit, which is located within its housing.
Number of
flashes red LED Conditions Action
2 Undervoltage (Ue
<190VAC
1)
)
1) <190 VACrms+/-2% at 1 s.
Auto reset with 5 min.
recovery
2)
2) Contact network supplier if alarm remains.
3 Overcurrent during
start-up (>80A for 1 s.)
Auto reset with 5 min.
recovery
4 Relay protection User action/possible
replacement of unit
5 Incomplete ramp Auto reset with 5 min.
recovery
Table 170
If the same alarm is repeated even after manual restart,
the unit should be replaced (refers to 4 and 5 flashing
alarms).
Behaviour Function
Blue, continuously lit. The heat pump is running.
Blue, flashing rapidly. There is an alarm which must be
acknowledged.
The alarm has been acknowledged but the
alarm cause remains.
Blue, flashing. The heat pump is in standby mode
1)
.
1) Stand-by means that the heat pump is running but no heating or hot water
demand exists.
Table 171 Alarm lamp control unit