SETTINGS
6 720 806 768 (2013/02)46
At a temperature higher than 20 °C, the same curve value applies as for
20 °C.
>> Highest permitted flow temperature T1
1)
The value that is set in Lowest permitted flow temperature T1.
>> Lowest permitted flow temperature T1
Set the highest and lowest permitted temperature for T1. Ensure that
the value corresponds with the selected curve and possible curve
adjustments.
Check also that the highest temperature T1 with Underfloor does not
exceed the permitted value for the type of floor used.
>> Heat curve
The settings are the same as for Circuit 1.
>> Room sensor (room controller)
The settings are the same as for Circuit 1.
>> Room temperature program
The settings are the same as for Circuit 1, except that Copy to all
heating circuits is not included.
>> Regulator settings
The mixing valve is controlled with PID regulator in order to reach the
flow set point value when there is a need. The signal determines how
much the opening of the mixing valve should change. It is calculated with
short time intervals.
>> Regulator settings
>>> P constant
>>> I constant
>>> D constant
>>> Minimum PID signal
>>> Maximum PID signal
>>> Mixing valve running time
Set the run time that is indicated on the mixing valve and indicate
value in number of minutes.
>>> Mixing valve fully closed
Set how many K ( °C) below the maximum permitted flow temperature
T1 the mixing valve is to be fully closed. The maximum flow
temperature is different depending on the type of heating system
(radiator or underfloor). With an underfloor system, the mixing valve
should be fully closed at 45 °C-2K=43 °C (with factory settings).
>>> Mixing valve start closing
Set how many K ( °C) below the value for fully closed mixing valve the
closure of the mixing valve should begin. The result is 43 °C-2K=41 °C
(with the factory settings for underfloor heating).
The right point of the curve (-35 °C) can be changed in
Minimum outdoor temperature ( Chapter 20.1).
Set value applies for all heat curves.
A change of the right point affects the flow temperature
for all outdoor temperatures that are lower than the set
temperature.
Factory setting 80.0 °C
Lowest value
1)
Highest value 100.0 °C
Table 60 Radiator
Factory setting 45.0 °C
Lowest value
1)
Highest value 45.0 °C
Table 61 Underfloor
Factory setting 10.0 °C
Lowest value 10.0 °C
Highest value 80.0 °C
Table 62 Radiator
Factory setting 10.0 °C
Lowest value 10.0 °C
Highest value 45.0 °C
Table 63 Underfloor
Factory setting 1.0
Lowest value 0.1
Highest value 30.0
Table 64 P constant
Factory setting 300.0
Lowest value 5.0
Highest value 600.0
Table 65 I constant
Factory setting 0.0
Lowest value 0.0
Highest value 10.0
Table 66 D constant
Factory setting 0%
Lowest value 0%
Highest value 100%
Table 67 Minimum PID signal
Factory setting 100%
Lowest value 0%
Highest value 100%
Table 68 Maximum PID signal
Factory setting 300s / 05:00
Table 69 Mixing valve running time
If there is no time indication on the mixing valve, run it
manually ( Chapter 20.7) and measure how long it
takes to go from fully closed to a fully open mixing valve
(the mixing valve stops sounding and the endposition
switch switches off).
Factory setting 2.0K
Lowest value 1.0K
Highest value 10.0K
Table 70 Mixing valve fully closed
Factory setting 2.0K
Lowest value 1.0K
Highest value 10.0K
Table 71 Start closing mixing valve