SETTINGS
6 720 806 768 (2013/02)54
>>> Mixing valve signal
>>> Mixing valve open
>>> Mixing valve close
>> Alarm buzzer
>> General alarm
> Circulation pumps
>> Heating circuit pump G1
>>> Operation alternative
Select if circulation pump G1 should run continuously or in optimised
operation. The setting applies to G1 of all circuits.
Continuous means that G1 is always in operation during the heating
season.
Automatic means that the circulation pump runs in approx. 10 min,
stands idle for 10 min, and so on, if it is in winter operation and there
has not been any heating demand for 40 min. Automatic operation is
cancelled when heating demand arises or winter operation is
disabled.
G1 stands idle (apart from anti-seizure operation) if it is summer
operation.
>> Heat carrier pump G2
>>> Operation alternative
Select if heat carrier pump G2 should run continuously or start
automatically when the compressor starts.
The setting applies to all heat pumps' G2. In automatic operation, G2
starts for heat pump 2 when compressor 2 starts.
>>> Pump speed E2x
>>>> Fixed pump speed
Set desired percentage to maintain a constant pump speed. Auto
means the pump speed will be controlled by the control unit.
>>>> Temperature difference heat transfer fluid when heating
Specify the temperature difference which the heat pump will aim to
achieve. This is done by regulating the pump speed.
>>>> Temperature difference heat transfer fluid when hot water
Specify the temperature difference which the heat pump will aim to
achieve. This is done by regulating the pump speed.
>>>> Pump speed at no demand
Set pump speed when there is no demand. A low speed is used to
keep the system operating when there is no demand for heat.
>>> Regulator settings
>>>> P constant
>>>> I constant
>> Collector circuit pump G3
>>> Operation alternative
Select if collector circuit pump G3 should run simultaneously with the
compressor or continuously.
> Screed drying
The screed drying function is used to expel humidity from the floor tiles
in newly-built houses. The drying program has the highest priority, i.e.,
all other functions than security functions and additional heat only are
disabled. All circuits contribute to the drying.
Screed drying takes place in three phases:
•Heating phase
Phase with maximum temperature
•Cooling phase
Heating and cooling are performed stepwise; each step continues for at
least a day. The phase with maximum temperature is considered to be
one step. There are 9 steps with the factory values: Heating phase in 4
steps (25 °C, 30 °C, 35 °C, 40 °C), maximum temperature (45 °C for
four days), cooling phase in 4 steps (40 °C, 35 °C, 30 °C, 25 °C).
It is possible to cancel a running program. On completion of the program,
the heat pump returns to normal operation.
>> Activate
▶Select Yes if drying should be performed.
There is an opportunity to change the current program step.
>> Remaining time for current step (shown if drying is enabled)
Factory setting Continuous
Alternative Continuous/Automatic
Table 124 G1
Factory setting Automatic
Alternative Continuous/Automatic
Table 125 G2
Factory setting Auto
Lowest value 0% (Auto)
Highest value 100%
Table 126 Fixed pump speed
Factory setting 7K
Lowest value 3K
Highest value 15K
Table 127 Temperature difference heat transfer fluid when heating
Factory setting 7K
Lowest value 3K
Highest value 15K
Table 128 Temperature difference heat transfer fluid when hot water
Factory setting 10%
Lowest value 1%
Highest value 100%
Table 129 Pump speed at no demand
Factory setting 3.0
Lowest value 0.1
Highest value 30.0
Table 130 P constant
Factory setting 300.0
Lowest value 5.0
Highest value 600.0
Table 131 I constant
Factory setting Automatic
Alternative Continuous/Automatic
Table 132 G3
Screed drying requires the installation of underfloor
heating coils under the floor tiles. Consult with screed
manufactories for information on maximum
temperatures and time required.
Factory setting No
Alternative Yes/No
Table 133 Activate screed drying