CONTROL PANEL
6 720 806 768 (2013/02) 35
15 CONTROL PANEL
Settings for the control of the heat pump are made with the control unit's
control panel, which also provides information about current status.
15.1 PANEL OVERVIEW
Fig. 42 The control panel
[1] On/Off button
[2] Mode button
[3] Info button
[4] Menu dial
[5] Status lamp
[6] Return button
[7] Menu button
[8] Menu display
15.2 ON/OFF BUTTON
Use the On/Off button to turn the heat pump on and off.
15.3 STATUS LAMP
15.4 MENU DISPLAY
Use the menu display in order to:
View information from the heat pump.
View available menus.
Change set values.
15.5 MENU BUTTON AND MENU DIAL
Use to get from the Initial menu to the menus. Use the menu dial in
order to:
Navigate the menus and get to the setting displays.
Turn the dial to see more menus on the same level or change a set
value.
Press the dial to change to a lower menu level or save a change.
15.6 RETURN BUTTON
Use to:
Go back to the previous menu level.
Leave a setting display without changing the set value.
15.7 MODE BUTTON
Use to change type of operation.
Change type of operation.
15.8 INFO BUTTON
Use to see information from the control unit about operating
mode, temperature, program version, etc.
16 START UP
The first time the heat pump is started, a number of settings are
displayed automatically so as to facilitate putting it in operation.
Before this stage, the heat pump should be installed in accordance with
the previous sections ( Chapter 13,
Chapter 14). Collector circuits, heating circuits and hot water
circuits should be filled and vented.
The settings are also available under ordinary installer menus.
LANGUAGE, COUNTRY, OPERATING MODE AND ELECTRICAL
CONNECTION
Select language for the menus of the control unit
( Chapter 20.10).
▶Select Country ( Chapter 20.10).
Select operating mode (L/W + electric additional heat)
( Chapter 8.4, Chapter 20.7).
▶Select Electrical connection (230V).
START-UP
Review and adjust, as required, the functions below. See the references
for description of the functions.
The lamp lights continuously. The heat pump is running.
The lamp flashes rapidly. There is an alarm that has not been
acknowledged.
The alarm has been acknowledged
but the alarm cause remains.
The lamp flashes slowly, menu
window not lit.
The heat pump is in stand-by mode
1)
.
1) Stand-by means that the heat pump is running but no heating or hot water
demand exists.
The lamp and menu display not
lit.
No voltage to the control unit.
Table 20 Lamp functions
The controller language can be changed with the
button.
Press the button in the initial menu for at least 5
s, then select the required language.
Only functions which are identified by the control unit
are displayed in the initial menu.
The start-up menus are available until Yes is entered in
Start-up completed.
Read the complete menus before start-up.
A selection must be made in Heat pump x capacity
and Protective anode installed.
With the -button, return to the previous menu
once settings have been made.
The selected system solution would normally require a
review of more settings than the ones in the start-up.