Zone normal: Activate Disarm
Wiring Diagram for Key-switch Zone: short for arm. The momentary time is capable of lasting
Min. 300ms.
Wiring Diagram for Key-switch Zone: short for arm. The momentary time is capable of lasting
Min. 300ms.
When the key-switch operates the Arm/Disarm, the keypad sounds two beeps and report sent
to the system by User Code 254
Notice!
As the key-switch operates the arm/disarm successfully, the siren sounds short to indicate it.
16 - Delay Exit
The delay exit zone will perform as below:
1. DISARM: Same as Instant zone disarm status
2. AWAY Arm:
– Zone normal - no Alarm / no report
– Zone triggered - Entry time starts - no Alarm / no report
– Disarming during entry time - no Alarm / no report
– Zone triggered - during exit time - no Alarm / no report / abbreviates remaining time
for exit to 5 s
– Zone triggered - during entry time - no Alarm / no report
– Zone triggered - entry time is expired - Alarm / report (report is delayed for 30sec,
when system is disarmed before, no report)
3. STAY ARM: Same as AWAY ARM performance.
– First delay zone will start the entry time; all other delay zones will follow.
– When System is disarmed and zone is not restored before, a Zone restore report is
sent.
17 - Interior Delay Exit
The Interior delay exit zone will perform as below:
1. Disarm: same as the Instant Zone disarm status
2. AWAY Arm: same as the Delay Exit Zone AWAY Arm status
3. STAY Arm:
– This Zone will be Ignored and performed as disarm.