DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 117
Bosch Security Systems | 8/04 | 4998153891C
Mode (Steady, Pulse, One Shot), Output ##
• Address: See Table 24 on page 110
• Default:
− Outputs 1 to 4: 1 (Steady)
− Outputs 5 to 20: 0 (Disabled)
• Selections: 1 to 13 (see Table 26)
There are two types of outputs: state-driven outputs and event-driven outputs. State-driven outputs follow the
state of a condition, either on or off. For example, a state-driven output is Type 0|1 Armed. The output is active
when the control panel is armed and inactive when the control panel is disarmed.
Event-driven outputs follow events when they occur. These events have no On or Off state. For example, an
event-driven output is Type 0|13 Ack Received. When the key is pressed, the output is activated.
Table 26 describes the mode operation for both on-board and off-board outputs.
Table 26: Output Mode Options
Mode Mode Type Output
Type
Description
State Output turns on when the condition is active and turns off when the condition is
inactive.
1 Steady
Event Output turns on when the event occurs. [System Reset] turns the output off.
State Output turns on when the condition is active and remains on until [System Reset] is
pressed.
2 Latch
Event Output turns on when the event occurs and remains on until [System Reset] is
pressed.
State When the condition goes from inactive to active, the output changes state. The
condition going from active to inactive has no effect.
3 Toggle
Event Whenever the event occurs, the output changes state.
State When the condition is active, the output pulses. When the condition is inactive, the
output is off.
4 Pulse
Event When the event occurs, the output pulses. The output remains pulsing until [System
Reset] is pressed.
State When the condition changes from inactive to active, the output turns on. The output
turns off at the end of the One-Shot time. While the output is on, any changes in the
condition are ignored.
5 One-Shot
Event When the event occurs, the output turns on and remains on for the One-Shot time.
When the output is on, a second event does not affect the output.
State When the condition changes from inactive to active, the output turns on and remains
on for the One-Shot time. If the condition goes inactive and active again, the One-Shot
time is restarted and the output remains on.
6 One-Shot
with Re-
Trigger
Event When the event occurs, the output turns on and remains on for the One-Shot time. If a
new event occurs when the output is on, the One-Shot time is restarted and the output
remains on.
State When the condition changes from inactive to active, the output turns on and remains
on for the One-Shot time. If the condition goes inactive, the output is turned off early.
7 One-Shot
with Reset
Event When the event occurs, the output turns on and remains on for the One-Shot time.
[System Reset] turns the output off early.
State Output turns on when the condition is inactive and turns off when the condition is
active.
8 Steady,
Reversed
Logic Normal
Event Output turns off when the event occurs. [System Reset] turns the output on.
Commentaires sur ces manuels