48 en | Installing AMC2 4W | Installation manual
F.01U.024.965 | V 0.1 | 2006.03 Bosch Sicherheitssysteme GmbH
1. Door open:R
S
+ R
P
2. Door closed:R
S
3. Broken wire:R
S
+ R
P
=
4. Short circuit:R
S
+ R
P
= 0
The resistor values can vary and
depend on the used lock system
(wire resistance negligible).
Default values are:
R
S
= 2,2 k
R
P
= 4,7 k
Fig. 5.23 Operating modes of a lock using the analog input device
i
NOTE!
A complete connection diagram of the analog input devices is
shown in chapter Section 7.1 Connecting Diagrams of this docu-
mentation.