K2200 Series | Installation Guide | 6.0 Configuration and Testing EN | 52
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
Figure 34: Line Driver Wiring Diagram
Fitting the Line Driver
For effective communications, you must
ensure that both the interface unit and
the door controller are properly
grounded.
The line driver should be plugged directly into the
door controller’s RS-232 port, the 5-way socket at the
bottom right of the circuit board.
The connection to the interface unit is made by
connecting the terminals labeled A B C D to the
corresponding terminals in the interface unit. Use the
4-pin terminal blocks provided.
If communications are successfully established, you
should a polling indication:
1
The 1 at the far right of the display means the PC
system is communicating with the door controller.
From now on:
• All updates must be made from the PC.
• All transactions, including alarms, are sent to the
PC.
6.2.3 Connecting a Modem
Multi-Site CNC See Readykey K6100 Central Network
Controller Installation Guide (Bosch P/N: 46512, PAC
P/N: 17163) for details of communicating with a door
controller over public (PSTN) phone lines, the types
of modems you can use and door controller
configuration.
The modem should be installed close to the door
controller and connected using the cable described in
Figure 35.
Modem to Readykey K2200 Series Cable
Use 24 AWG (0.5 mm), 6-conductor, unshielded
cable, maximum length: 50 ft. (15 m).
Figure 35: Modem to Readykey K2200 Series
Cable
Modem Door Controller
in male D-type connector 5-pole terminal block
TX 2
------
TX
RX 3
------
RX
GND 7
------
GND
CTS 5
------
CTS
RTS 4
DTR 20 DTR
Pin 4 and 20 are twisted together and connected
to the DTR terminal at the controller.