36 en | Installing AMC2 4W
F.01U.024.965 | V.4 | 2006.09 Installation manual Bosch Security Systems
5.7 RS-232 Host Interface
The AMC2 4W offers an RS-232 serial interface to connect a
host computer or serial modem.
Address
DIL Switches
1234
none OFF OFF OFF OFF
1 ON OFF OFF OFF
2OFFON OFF OFF
3 ON ON OFF OFF
4OFFOFFON OFF
5 ON OFF ON OFF
6OFFON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
Table 5.1 Setting the RS-485 address with the DIL switch
Mode
DIL Switches
56
ON SDEB RS-232
OFF BPA RS-485
Table 5.2 Protocol and connection settings
!
CAUTION!
Cable length between two RS-232 COM serial interfaces must
not exceed 15 meters (45 ft).