D7212GV2 | Operation and Installation Guide | 4.0 Installation
18 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
4.6.3 Installing Modules and Relays
1. Power down the unit by unplugging the
transformer and disconnecting the battery.
Always power down the unit when installing
modules or relays, or when making wiring
connections to the control panel.
2. Install and wire any modules required for the
installation as described in the module’s
installation instructions.
Instructions for the D8125 POPEX Module,
D8128D OctoPOPIT Module, D8129 OctoRelay
Module, and D811 Arm Status Relay Module
appear in this guide.
Refer to Section 9.0 Off-Board Points on page for
D8125 and D8128D instructions. Refer to Section
10.0 Off-Board Relays on page 44 for D8129 and
D811 instructions.
3. If using the power outputs at Terminals 7 or 8,
refer to Section 6.4 Programmable Power Output
Terminals 6, 7, and 8 on page 25 for instructions.
4.6.4 Connecting the On-board Points and
Keypads
Connect the on-board points and keypad wiring to the
system. Refer to Section 8.0 On-Board Points on page 29
and Section 11.0 Arming Devices on page 46 for
instructions.
4.6.5 Powering Up
Reconnect the battery, then plug in the transformer.
The buzzer sounds for two seconds when the control
panel is powered up. Leave the reset pin in the locked
position.
Yellow Charging Status LED Remains Lit: If the
yellow charging status LED remains lit after five
minutes of powering up the control panel, either the
battery is deeply discharged, or too many powered
devices were connected to the control panel.
Combined continuous current draw for Terminals 38,
24, and 32, and the accessory connector cannot exceed
1.4 A. Refer to Section 6.0 Power Outputs on page 25 for
help.
4.7 Programming the Control Panel
If the control panel is not already programmed, review
the D7212GV2 Program Entry Guide (P/N:
F01U003804). Ensure that all accessory modules for
desired features are available for installation. Place the
reset pin in the locked position to copy or send
information to and from the control panel.
Use the D5200 Programmer or the RPS to load a
custom program into the control panel.
Move the reset pin to the normal position (refer to
Figure 6 on page 17). The control panel sends Reboot
and Battery Reports to the receiver if programmed for
reporting
4.8 Installing the Point Chart Label
The point chart label is required for fire
systems with verifications points.
A point chart label is included in the literature pack.
Install the point chart label for fire or combined fire-
and-burglary systems that use verification points.
Use the D7212GV2 Program Record Sheet
(P/N: F01U003803) to gather the necessary information
for completing the point chart. Fill out the label and
install it on the inside of the enclosure door (refer to
Figure 2 on page 14).
Avoid smearing the entries on the chart.
Use the peel-off backing to press the label
in place.
4.9 Testing the System
After installing and programming the control panel,
test the system completely. Test the control panel and
all devices for proper operation.
Test after initially programming the control
panel and after subsequent programming
changes.
Refer to Section 4.10 Service Walk Test for complete
Service Walk Test instructions.
Clear after Test: To clear the event memory and
report buffer, momentarily close the reset pin. Events
stored in the control panel’s event log are not cleared.