Intrusion Alarm Systems | D7412GV4 Series Control Panels
D7412GV4 Series Control Panels
www.boschsecurity.com
u Fully integrated intrusion, fire, and access control
allows users to interface with one system instead of
three
u Conettix IP‑based communication options provide
high‑speed, secure alarm transport and control
through connection of wired and/or wireless cellular
network interfaces
u Up to 8 programmable areas each supporting both
with perimeter and interior points with your choice
of touch screen, ATM style, or LED keypads
u 75 points with flexible configuration options to meet
multiple installation requirements
u OPTIONAL GV4 version 2.00 firmware upgrade
available (NEW)
GV4 panels are the premier commercial control panel
line from Bosch. GV4 panels integrate intrusion, fire
and access control providing one simple user interface
for all systems. With the ability to adapt to large and
small applications, the D7412GV4 provides up to 75
individually identified points that can be split into 8
areas. The control panel includes a communicator that
sends events to selected public switched telephone
network (PSTN), IP network, or cellular network
destinations through four programmable route groups.
With the D7412GV4 you can:
Monitor alarm points for intruder or fire alarms while
operating keypads and other outputs
Program all system functions local or remote using
Remote Programming Software (RPS) or by using
basic programming through the keypad.
Add up to two doors of access control using the
optional D9210C Access Control Interface Module.
Functions
Programmable Outputs
2 A alarm power at 12 VDC
1.4 A auxiliary power at 12 VDC
Four alarm‑output patterns
Programmable bell test
System Response
High-performance micro‑controller provides
industry‑leading system response
High-speed device bus (NEW)
31 custom point indexes, including fire supervisory
Selectable point response time
Cross point capability
Fire alarm verification
Fire inspector’s local test
Watch mode
Scheduled events (SKEDs) arm, disarm, bypass and
unbypass points, control relays, control authority
levels, and control door access
User Interface
Supervision of up to 16 keypads (up to 32
unsupervised keypads can be used)
Remote Programming Software (RPS) Lite allows end
users to perform control panel management tasks –
Add/Delete/Change user passcodes and authorities,
view and print the panel history event log
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 -

Intrusion Alarm Systems | D7412GV4 Series Control PanelsD7412GV4 Series Control Panels www.boschsecurity.com u Fully integrated intrusion

Page 2

• Custom keypad text is fully programmable, includingremote programming• Full function command menu including CustomFunctions• Authority by area and 1

Page 3

IP Setup is available via the installer keypad menusand the remote programming software, eliminating theneed to use complicated internet programming t

Page 4 - Compatible Products

ANSI/SIA CP-01:2010 False Alarm ReductionCSFM California Office of The State Fire Marshall7165-1615:0242 Control Unit(Commercial)FM 3010 FCC Part 15

Page 5 - Parts included

D8125MUX Point ExpanderD8125INV Wireless Interface ModuleD8129 Octo‑relay ModuleD8130 Door Release ModuleD9127 Series POPIT ModulesD9131A Parallel Pri

Page 6

D8109 Fire Enclosure 1 Technical specificationsCommunicationsTelephoneConnection:• One telephone line• D928 Dual Phone Line Module required fortwo

Page 7

D1224 Battery (12 V, 26‑28 Ah)A 12 V sealed lead‑acid battery for standby andauxiliary power with two bolt‑fastened terminals.Includes hardware for at

Page 8

8 | D7412GV4 Series Control PanelsRepresented by:Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:Bosch Security Systems, In