D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0 Off-Board Points
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 45
Figure 19: Program Record Sheet
EN | 25
bold
Point Assignments (001 through 040)
POPIT Switch
Setting
Trans-
lation
Point
#
Point
Index
Area
Assign
Debounce
BFSK/
Relay
Custom Point Text
100 001 (3) _ _ (1) ___ (2) _____ (1) ____
P1 FIRE
___________________
200 002 (1) _ _ (1) ___ (2) _____ (2) ____ P2 PANIC ___________________
300 003 (25) _ _ (1) ___ (2) _____ (3) ____ P3 DELAY ___________________
400 004 (13) _ _ (1) ___ (2) _____ (4) ____ P4 FOLLOW ___________________
500 005 (7) _ _ (1) ___ (2) _____ (5) ____ P5 INSTANT ___________________
600 006 (7) _ _ (1) ___ (2) _____ (6) ____ P6 INSTANT ___________________
700 007 (7) _ _ (1) ___ (2) _____ (7) ____ P7 INSTANT ___________________
800 008 (7) _ _ (1) ___ (2) _____ (8) ____ P8 INSTANT ___________________
0 1 2 3 4 5 6 101 009 __ __ (1) ___ (2) _____ (1) ____ P9 ___________________
Default values are shown in ( ) or in bold
D9412GV2/D7412GV2 | Program Record Sheet | RADXPNTS Handler
9.3.8 POPIT Labels
D9412GV2 off-board points are numbered 9 to 127
and 129 to 247. The D7412GV2 uses Points 9 to 75
only. The D9412GV2 reserves Points 128 and 248 for
internal use. POPITs must be connected for Points
129 to 247 to expansion loops connected to POPEX
#2.
Two sheets of peel-off POPIT labels are supplied with
the D8125 POPEX Module. Use the sheet marked
“Bank1” for Points 9 to 127. Use the sheet marked
“Bank2” for Points 129 to 247.
Each label has two parts. Place the smaller part (with
only the point number) on the chip. Place the larger
part with the switch settings on the base of the
POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point
number. After programming all the points, perform a
Service Walk Test. Refer to Section 4.10 Service
Walk Test on page 47. If a point does not test, check
the programming for a duplicated address.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, missing and
extra points can occur. If the same point number is
assigned to two or more POPITs or OctoPOPITs,
none of the points with that number test correctly.
Refer to Section 9.1 Point (Zonex) Bus: D9412GV2
Terminals and D7412GV2 Terminals on page 39.
For UL 864 Commercial Fire applications,
refer to Installing Combination Fire and
Intrusion Alarm Systems in the
D9412GV2/D7412GV2 Approved
Applications Compliance Guide
(P/N: F01U003639) for important
information about combination fire and
intrusion systems.
9.4 D8128D OctoPOPIT Module
Modules D8128, D8128A, or D8128B are
incompatible with the D9412GV2 or
D7412GV2. Use only the D8128D
OctoPOPIT Module. Using Modules
D8128, D8128A, or D8128B can cause
intermittent Missing and Restoral Reports.
9.4.1 Description
The D8128D OctoPOPIT Module combines the
functions of the D8125 POPEX Module and the
D8127/D9127 POPIT Modules to provide eight off-
board points in a single module. You can wire both
D8128D OctoPOPIT and D8125 POPEX Modules in
parallel to the Zonex Bus terminals on the same
control panel.
Review Section 6.0 Power Outputs on page 28 to
ensure that there is enough power for the
OctoPOPITs and other powered devices that will be
connected to the system.
Up to thirty D8128D Modules can be connected to the
D9412GV2 Control Panel. Up to nine D8128Ds can
be connected to the D7412GV2 Control Panel (three
points can be used on the last OctoPOPIT).