28CDi RSF
WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING
AND MAINS FED DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
GC NUMBER 47 311 34 (N.G.)
GC NUMBER 47 311 35 (L.P.G.)
BOILER OUTPUT
Automatic Modulating Control
To Domestic Hot Water To Central Heating
Minimum 9.0 kW 9.0 kW
Maximum 28.0 kW 24.0 kW
IMPORTANT: THESE INSTRUCTIONS APPLY IN THE UK ONLY
THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER
This appliance must be installed by a competent person in accordance
with the Gas Safety (Installation and Use) Regulations 1994
Bosch Group
Vue de la page 0
1 2 3 4 5 6 ... 35 36

Résumé du contenu

Page 1 - 28CDi RSF

28CDi RSFWALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATINGAND MAINS FED DOMESTIC HOT WATERINSTALLATION ANDSERVICING INSTRUCTIONSGC NUMBER 47 311 34

Page 2 - Contents

10Fig. 10. Functional flow diagram. MainsindicatorOn/OffswitchST8(LS)ST8(LR)ST8(NS)ST1CentrePinST15Pin LST1Pin LREL 1 REL 3HighLowREL4PumpFan(2 speed)

Page 3 - Fig. 1a

11Fig. 11. 230 V room thermostat connections.Fig. 13. 230 V room thermostat andprogrammer connections.Fig. 12. 230 V programmer connections.NS LSST8ST

Page 4 - 3. Technical Data

The appliance is supplied suitable for fitting to a sealed system. Ifit is to be fitted to an open vent system refer to section 8.11.1 FLUE OPTIONS.Th

Page 5 - 4. Siting The Appliance

NOTE: READ THIS SECTION FULLY BEFORE COMMENCINGINSTALLATION11.2 GENERAL FITTING.Check that the appliance carton contains: Appliance, installersinstruc

Page 6

ducts into the flue outlet turret.Pull back the air duct slightly to allow access to the flue duct.Drill through the flue duct and fix with the screws

Page 7 - 7. Sealed Primary Systems

Align the flue turret with the 4 holes on the appliance and screwdown. See Fig. 16.Refit the fan. Do not use any sealant on the joint. Replace theinne

Page 8 - 9. Domestic Hot Water

12.1 SUMMARYThe appliance is dispatched with the controls set to provide amaximum output for domestic hot water of 28 kW and 24 kW forcentral heating.

Page 9 - 10. Electrical

Set the movable pointer on the pressure gauge to coincide withthe indicating pointer giving a permanent record of the setsystem pressure.If the pressu

Page 10 - (2 speed)

13.1 Tell the user how to operate the appliance and hand overthe Users Instructions leaflet.13.2 Tell the user what to do if the heating system is not

Page 11 - Switched live

assembly from the appliance. See Fig. 28. When refitting thehood ensure that the rear return edge passes under the lip at therear of the combustion ch

Page 12 - 11. Installation

1.1 Gas Safety (Installation and Use) Regulations, October 1994all gas appliances must be installed by a competent person inaccordance with the above

Page 13

AIR PRESSURE SWITCH2. Air Flow Pressure Switch.See Fig. 30.Check that the electricity supply to the appliance is turned off.Remove the cabinet front

Page 14

13. Central Heating Sensor. See Fig. 31.Remove the inner casing cover as described in Section 14.3(b).Check that the electricity supply to the applian

Page 15 - Flue and air

2216. Short Parts ListAccessories For 28CDi RSF26 378 312 Gas Valve Junkers Bosch, Type CE 426 1 8 747 003 366 078 E00-720 Burner – Natural Gas Aeroma

Page 17

17 Operational Flow Diagrams24

Page 20

18. Fault Finding27Note: This fault-finding information is for guidance only. Worcester Heat Systems cannot be held responsible for costs incurred byp

Page 23

The boiler requires 3.35 m3/h (115 ft3/hr) of natural (G20) or 1.29m3/hr (46 ft3/hr or propane gas (G31). The gas meter and supplypipes must be capabl

Page 30

This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in

Page 31

The data plate is fixed to the inner casing cover. Check data plateto ensure appliance has been adjusted for supply gas.3. Technical Data4AVAILABLE PU

Page 32

4.1 The appliance may be installed in any room althoughparticular attention is drawn to the requirements of the currentI.E.E. Wiring Regulations BS 76

Page 33

See Fig. 45.1 The flue must be installed as specified in BS 5440:Part 1.5.2 The terminal must not cause an obstruction nor thedischarge cause a nuisan

Page 34

See Figs. 5, 6 and 6a.7.1 The system must comply with the requirements of BS 6798and BS 5449.7.2 The appliance must not be operated without the system

Page 35

8.1 The size of the flow and return pipework is given in Section 3– Table 4. The components required to connect the appliance toan open vent system ar

Page 36 - Bosch Group

See Figs. 8, 9, 10, 11, 12 and 13.10.1 MAINS SUPPLY.230 V ~, 50 Hz, 180 watts.External Fuse: 3A. Internal Fuses: T 2A (F1), and T 1.25A (F2).Spare in