Installation Instructions
D296 and D297
Long Range Beam Smoke Detectors
1.0 Description
The D296 and D297 are long range projected beam type smoke
detectors which consist of a separate transmitter and receiver. Internal
pointability provides coverage flexibility without the need for brackets.
Automatic Signal Synchronization and Range Adjustment reduce
installation costs. Selectable sensitivity and alarm response time
provide installation flexibility.
2.0 Specifications
Operating Voltage: D296: 18.0 to 32.0 VDC
D297: 10.2 to 15.0 VDC
Standby Current: D296: Receiver - 45 mA @ 24.0 VDC
Transmitter - 20 mA @ 24.0 VDC
D297: Receiver - 50 mA @ 12.0 VDC
Transmitter - 20 mA @ 12.0 VDC
Receiver Alarm
Current: D296: 60 mA @ 24.0 VDC
D297: 75 mA @ 12.0 VDC
Range (distance
between transmitter
and receiver): 30 to 350 ft. (9 to 107 m)
Spacing (distance
between systems): Allow no more than 60 ft. (18 m) between
systems. Sixty foot spacing is confirmed
by Underwriters Laboratories, Inc. testing.
Pointability: Internally pointable optics for ±90°
horizontal, and ±10° vertical adjustment.
Sensitivity: Field selectable for 20, 30, 40, 50, 60, or
70 percent beam obscuration.
Alarm Contacts: Normally Open contacts rated 1 amp,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.
Trouble Contacts: Normally Closed contacts rated 1 amp,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.
Aux. Alarm
Contacts: Form "C" (NO, C, NC) contacts rated
1 amp, 60 VDC maximum for DC resistive
loads. Do not use with capacitive or
inductive loads.
Tamper: Receiver: Access door tamper switch in
series with trouble contacts.
Transmitter: Upon cover’s removal, cover
tamper switch interrupts
transmission.
System Signaling: Conventional 4-wire system. Not for use
with systems that incorporate an alarm
verification feature.
Signal Delay: Fire: Selectable 30 seconds or 5
seconds
Trouble: 20 ± 2 seconds.
Temperature: The storage and operating temperature
range is -22° to +130°F (-30° to +54°C).
For UL Listed installations, the range is
+32° to +130°F (0° to +54°C).
Mounting: The units are designed to be mounted to
4 in. (10 cm) square or octagonal
electrical boxes (not supplied).
Listings and
Approvals: UL S3019
ULC CS692
MSFM Permit #1943
NY City MEA Acceptance #MEA274-93-E
CSFM #7260-1062:106
FM Job #OX2A9.AY
Standard
Accessories: D306 Remote Test/Indicator Plate and
Test Cable
Options: D307 Remote Indicator Plate, D308
Field Test Kit, D309 Alignment Light, and
D1005 Test Cord.
3.0 Principle of Operation
Each D296 or D297 beam smoke detector has a separate transmitter
and receiver. The transmitter transmits an invisible infrared beam of
a specific frequency and intensity. The receiver detects, then measures
the beam’s intensity (see Figure 1).
Figure 1 - Infrared Transmission
As the beam is obscured by smoke, the receiver senses a decrease
in the signal strength and measures that decrease. The receiver
compares the signal level with two preset thresholds: an alarm
threshold which is set using the sensitivity switch and a trouble
threshold which is preset at approximately 10%. If the signal falls
below the alarm threshold for the programmed alarm period, the
receiver signals an alarm (see Figure 2).
Figure 2 - Beam Obscuration
If the signal falls below the trouble threshold for more than 20 seconds,
such as might happen if the beam is blocked by a foreign object, the
receiver signals a trouble condition (see Figure 3).
Figure 3 - Beam Blockage
The receiver automatically compensates for the gradual loss of signal
due to dust/dirt build-up on the cover. After 50 percent of the signal is
lost, the receiver will indicate a trouble. When the dust/dirt build-up is
cleaned or the blockage is removed, the detector automatically goes
back to its normal operation level.
A trouble will be indicated at the receiver if the beam strength is
increased by more than 20% for greater than 20 seconds. Causes
include improper initial alignment or the removal of a partial beam
blockage at the time of alignment. Preform a fine-tune alignment
(see Section 7.3).
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - 3.0 Principle of Operation

Installation InstructionsD296 and D297Long Range Beam Smoke Detectors1.0 DescriptionThe D296 and D297 are long range projected beam type smokedetector

Page 2

D296/D297 Installation InstructionsPage 10 31344D Copyright © 2002 Radionics10.0 Installing Multiple Units

Page 3 - 5.0 Mounting

D296/D297 Installation InstructionsCopyright © 2002 Radionics 31344D Page 1111.0 Quick Start Installation Flow ChartStartTX = TransmitterRX = Receive

Page 4 - 7.0 SET-UP

© 2002 Radionics, a division of Detection Systems, Inc. 31344D 02/02PO Box 80012, Salinas, CA 93912-0012 USA Installation Instructions D296/D297Custom

Page 5 - Front Bore Sigh

D296/D297 Installation InstructionsPage 2 31344D Copyright © 2002 Radionics4.0 Installation ConsiderationsThe proper location and spacing of det

Page 6 - 8.0 Other Information

D296/D297 Installation InstructionsCopyright © 2002 Radionics 31344D Page 34.4 Provide a stable mounting surfaceBeam smoke detectors depend on the me

Page 7 - 30% 40% 50%

D296/D297 Installation InstructionsPage 4 31344D Copyright © 2002 Radionics6.0 WIRINGOnly apply power after all connections have been madeand in

Page 8

D296/D297 Installation InstructionsCopyright © 2002 Radionics 31344D Page 5AIM MODEBUTTONGREENLEDFigure 8 - Cutout View of Transmitter Circuit Board

Page 9 - 9.0 Troubleshooting

D296/D297 Installation InstructionsPage 6 31344D Copyright © 2002 Radionics0Figure 13 - Sensitivity Switch• The recommended settings chart lists

Page 10

D296/D297 Installation InstructionsCopyright © 2002 Radionics 31344D Page 78.3 Reference Voltage CalibrationThe reference voltage of the detectors sh

Page 11

D296/D297 Installation InstructionsPage 8 31344D Copyright © 2002 RadionicsThe Sensitivity Test Kit (supplied) may be used to check the sensitiv

Page 12

D296/D297 Installation InstructionsCopyright © 2002 Radionics 31344D Page 99.0 Troubleshooting